Inspection
Inspection Details
Equipment ID
5758
5758
Inspection Date
10/30/2023
10/30/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Walter Tauchert
Walter Tauchert
Relief Valve Pressure
450
450
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
18
18
External ID
2fe0d548-876d-41e3-9192-3631ca148646
2fe0d548-876d-41e3-9192-3631ca148646
Location
MOOG Center for the Deaf
12300 S 40 Dr, St. Louis, MO
Phone: (314) 692-7172
12300 S 40 Dr, St. Louis, MO
Phone: (314) 692-7172
Owner
Attn: MOOG Center for the Deaf
MOOG Center for the Deaf
12300 S 40 Dr, St. Louis, MO 63141
Phone: (314) 743-4689
Email: gbellinger@moogcenter.org
MOOG Center for the Deaf
12300 S 40 Dr, St. Louis, MO 63141
Phone: (314) 743-4689
Email: gbellinger@moogcenter.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | A written maintenance control program shall be kept on site for each elevator. It shall include on site documentation of all applicable items listed in section 8.6.1.2.2. | 10/19/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV in pit is sealed, but not tagged. Provide testing. | 10/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Provide MCP. | 10/14/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Post Phase I instructions near f/f switch in the lobby. | 10/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Car top door operator missing a belt. Replace as needed. | 10/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Provide MCP. | 10/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Car top door operator, missing one belt. Provide. | 10/14/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 10/14/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 10/14/2025 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | OSV in pit is sealed, but not tagged. Need to provide testing | 10/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Car top door operator is missing belt | 10/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Car top operator is missing belt | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room |