Inspection
Inspection Details
Equipment ID
14495
14495
Inspection Date
10/25/2018
10/25/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Wayne Ingram
Wayne Ingram
Mechanic Name
Jamon Gray
Jamon Gray
Relief Valve Pressure
340
340
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
a299630b-9eef-4056-96c5-7428f06fcb22
a299630b-9eef-4056-96c5-7428f06fcb22
Location
Jordan Valley Parking Garage
815 E SAINT LOUIS ST, SPRINGFIELD, MO
815 E SAINT LOUIS ST, SPRINGFIELD, MO
Owner
Plaza Realty & Management Services LLC
815 E SAINT LOUIS ST, SPRINGFIELD, MO 65806-2417
815 E SAINT LOUIS ST, SPRINGFIELD, MO 65806-2417
Billing
Attn: Plaza Realty & Management Services LLC
815 E SAINT LOUIS ST, SPRINGFIELD, MO 65806-2417
815 E SAINT LOUIS ST, SPRINGFIELD, MO 65806-2417
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Cover for Light fixture missing exposing electric wireing | 3/16/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room. | 4/7/2021 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Have the fire extinguisher re-certified or replaced including a certification sticker or replace it with a new one as ;yours haven't been-certified since 2003. | 4/7/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | 4/22/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Replace the burnt out pit light. | 4/22/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Provide a MCP in the machine room. | 4/22/2022 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Out of Date | |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post updated certificate. | |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | 5 YEAR DUE ON OSV ON OF BEFORE NEXT INSPECTION | |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | PHASE 1 FIRE SERVICE KEY SWITCH INSTRUCTIONS NOT LEGIBLE | |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | UNIT MISSING DROP CEILING INSERTS MUST REPLACE OR PUT PROTECTIVE TUBING OVER LIGHTING |