Inspection
Inspection Details
Equipment ID
14497
14497
Inspection Date
10/25/2018
10/25/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Wayne Ingram
Wayne Ingram
Mechanic Name
Jamon Gray
Jamon Gray
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
27e5aabe-f3ec-4b63-8508-0ecd8c5c3d13
27e5aabe-f3ec-4b63-8508-0ecd8c5c3d13
Location
Jordan Valley Parking Garage
815 E SAINT LOUIS ST, SPRINGFIELD, MO
815 E SAINT LOUIS ST, SPRINGFIELD, MO
Owner
Plaza Realty & Management Services LLC
815 E SAINT LOUIS ST, SPRINGFIELD, MO 65806-2417
815 E SAINT LOUIS ST, SPRINGFIELD, MO 65806-2417
Billing
Attn: Plaza Realty & Management Services LLC
815 E SAINT LOUIS ST, SPRINGFIELD, MO 65806-2417
815 E SAINT LOUIS ST, SPRINGFIELD, MO 65806-2417
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.36 - Hydraulic Cylinders | 302.3 | No | No | Cylinder Packing leaking excessive | 3/16/2021 |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 210.13 | No | No | Phase ll instruction missing | 3/16/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | 4/7/2021 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Replace the burnt out light in the pit. | 4/22/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | 4/22/2022 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5 Gland Packing and Seals | Yes | No | Repack the leaking jack packing it is excessive. | 1/4/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Provide an MCP in the machine room | 4/22/2022 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Out of date | |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post updated certificate | |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | 5 YEAR TEST DUE ON OSV ON OR BEFORE NEXT INSPECTION | |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | UNIT MISSING DROP CEILING INSERTS MUST REPLACE OF PUT PROTECTIVE TUBING OVER LIGHTING |