Inspection
Inspection Details
Equipment ID
11706
11706
Inspection Date
11/8/2023
11/8/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Walter Tauchert
Walter Tauchert
Relief Valve Pressure
400
400
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
20
20
External ID
1b04b7e9-c189-41c9-84f0-b19b5f0af52b
1b04b7e9-c189-41c9-84f0-b19b5f0af52b
Location
Medical Arts Building
11115 New Halls Ferry Rd, Florissant, MO
Phone: (000) 000-0000
11115 New Halls Ferry Rd, Florissant, MO
Phone: (000) 000-0000
Owner
Attn: Metro Property Mgmnt, LLC
Metro Property Mgmnt, LLC
11115 New Halls Ferry Rd, Ste 301, Florissant, MO 63033
Phone: (000) 000-0000
Email: kevken13@hotmail.com
Metro Property Mgmnt, LLC
11115 New Halls Ferry Rd, Ste 301, Florissant, MO 63033
Phone: (000) 000-0000
Email: kevken13@hotmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Emergency phone shall work | 4/15/2019 |
| conversion | conversion | n/a | No | No | Current state operating certificate shall be displayed | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 5/6/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Repair pit light. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 6/23/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lights need to be 10 ft candles. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Repair drop ceiling and replace broken lights inside cab. | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Repair pit light. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated operating certificate in machine room. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 11/8/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Replace pit light. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Replace machine room lights. | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Provide existing pit light to work. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide code compliant machine room lighting. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Repair drop ceiling and cab lights. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Provide safe and convenient access to the elevator machine room. Numerous lights are out, trash litters the floor. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | No | No | Provide guard on car ceiling fan. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Cylinder scavenger hose is too short, replace with proper length hose. Place into jug. |