Inspection
Inspection Details
Equipment ID
8405
8405
Inspection Date
10/10/2018
10/10/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
5fed58e5-422f-4fd9-8753-ef1ffa497eca
5fed58e5-422f-4fd9-8753-ef1ffa497eca
Location
St. Joseph Family Guidance
724 N 22ND ST, SAINT JOSEPH, MO
724 N 22ND ST, SAINT JOSEPH, MO
Owner
St. Joseph Family Guidance
724 N 22ND ST, SAINT JOSEPH, MO 64506-2604
724 N 22ND ST, SAINT JOSEPH, MO 64506-2604
Billing
Attn: St. Joseph Family Guidance
724 N 22ND ST, SAINT JOSEPH, MO 64506-2604
724 N 22ND ST, SAINT JOSEPH, MO 64506-2604
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | post emergency evacuation of passengers procedure form inside machine room. | 8/2/2020 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys (Re-Inspection) | x | provide firefighter key in machine room or on site. | 9/2/2020 | |
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | test firefighter service monthly and provide written documentation in machine room or on site. | 8/2/2020 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | x | car door restrictor does not function. | 9/2/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.11.1 | Test and log firefighter operation monthly | 11/5/2021 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump pump shall be provided | x | Provide sump pump. Install sump pump and drain line. Oil alarm per local plumbing code. Drain line shall not directly connect with sewer. | 11/5/2021 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | Post In Case of Fire signage next to hall button fixture at each landing | 9/27/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | x | CAR DOOR RESTRICTOR DID NOT WORK | 7/17/2025 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.19 - Car Ride | 8.11.2.1.1(s) | CAR HAS A BAD SHAKE AS IT TRAVELS UP & DOWN THE HOISTWAY | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.6.4.14 Hoistway Access Switches | HOISTWAY ACCESS DID NOT WORK IN THE UP DIRECTION | |||
A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | phone not working bad phone board |