Inspection
Inspection Details
Equipment ID
1673
1673
Inspection Date
10/11/2018
10/11/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Bobby Joe Mehrens
Bobby Joe Mehrens
Relief Valve Pressure
440
440
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
c63fb07c-fde0-484e-8d3e-8ee0764e2379
c63fb07c-fde0-484e-8d3e-8ee0764e2379
Location
Prior Hall
17 S JEWELL ST, LIBERTY, MO
17 S JEWELL ST, LIBERTY, MO
Owner
William Jewel College
500 COLLEGE HL, LIBERTY, MO 64068-1843
500 COLLEGE HL, LIBERTY, MO 64068-1843
Billing
Attn: William Jewel College
500 COLLEGE HL # 1110, LIBERTY, MO 64068-1843
500 COLLEGE HL # 1110, LIBERTY, MO 64068-1843
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | Test and log firefighter operation monthly | |||
A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | Post emergency evacuation of passengers form inside machine room | |||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate inside machine room | |||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Test and log firefighter operation monthly | |||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current state operating certificate inside the machine room | |||
A17.1-1996 : Elevators | 3.9 - Floor and emergency identification numbering | 1001.2(c)(15) | Identify the inside of hoistway doors with a numeral corresponding to the landing floor | |||
A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x | Emergency light does not illuminate | 9/20/2021 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency bell does not operate | 9/20/2021 | |
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 1000.1b(3)(b) Metal Test Tag | Install metal test tag for periodic pressure relief test | |||
A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No MCP | |||
A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No maintenance records on site | |||
A17.1-1996 : Elevators | 3.9 - Floor and emergency identification numbering | 100.7 | Identify inside of hoistway doors with a numeral | |||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | State operating certificate not displayed in machine room | |||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1(a)(3) Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency bell does not operate | 8/10/2023 | |
A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x | Emergency light does not illuminate | 8/10/2023 | |
A17.1-1996 : Elevators | 3.9 - Floor and emergency identification numbering | 100.7 | Identify inside of hoistway doors with a numeral | |||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency light and bell do not operate | 10/23/2024 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | State operating certificate not displayed | |||
MO Minimum : Elevators | (I) - Pits | (I)8 | Adjust sump pump cover and reinstall. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Bottom directional switch not working, contact with buffers during test. |