Inspection
Inspection Details
Equipment ID
15005
15005
Inspection Date
11/6/2023
11/6/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
6c035b34-1419-419f-8e10-e3c213b530a5
6c035b34-1419-419f-8e10-e3c213b530a5
Location
Crider Health Center
1032 Crosswinds Ct, Wentzville, MO
Phone: (636) 332-6000
1032 Crosswinds Ct, Wentzville, MO
Phone: (636) 332-6000
Owner
Attn: Kevin O’Laughlin
Crider Center for Mental Health
1032 Crosswinds Ct, Wentzville, MO 63385
Phone: (636) 332-6000
Email: kolaughlin@compasshn.org
Crider Center for Mental Health
1032 Crosswinds Ct, Wentzville, MO 63385
Phone: (636) 332-6000
Email: kolaughlin@compasshn.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 Guards Between Adjacent Pits | No | No | Sump pump hole shall have a code compliant cover. | 12/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 12/28/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | The auxiliary power lowering operation shall be functional. | 1/6/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 11/6/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | All 3 units at location are due for category 5 testing of the overspeed valve in 2024. | 11/12/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Battery lowering shall work. Repair or replace. | 12/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.11 - Plunger and Cylinder | 3.18 | No | No | Jack packings are leaking. Repack/repair as needed. | 12/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean. Remove excess oil. | 12/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.3 - Operating control devices | 2.26.1.1 | No | No | The car operating panel fire service access door is damaged. Repair or replace as needed. | 12/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Battery Lowering shall work | 12/11/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.11 - Plunger and Cylinder | 3.18 | No | No | Jack packings are leaking | 12/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be lept clean/ Remove excess oil | 12/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.3 - Operating control devices | 2.26.1.1 | No | No | The car operating panel is damaged. Repair or Replace | 12/1/2025 |