Inspection
Inspection Details
Equipment ID
12260
12260
Inspection Date
11/7/2023
11/7/2023
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
410
410
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
22
22
External ID
3de788fc-3bba-4da4-a85a-d45ace4a46e9
3de788fc-3bba-4da4-a85a-d45ace4a46e9
Location
Life Care Center
3520 Chouteau Ave, St. Louis, MO
Phone: (314) 771-7667
3520 Chouteau Ave, St. Louis, MO
Phone: (314) 771-7667
Owner
Attn: Life Care Center
Life Care Center
3520 Chouteau Ave, St. Louis, MO 63103
Phone: (000) 000-0000
Email: gina_higgins@lcca.com
Life Care Center
3520 Chouteau Ave, St. Louis, MO 63103
Phone: (000) 000-0000
Email: gina_higgins@lcca.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide onsite maintenance documents. | 3/18/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 3/25/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Emergency/standby power operation of the elevator shall be tested. | 3/28/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | The presence of an overspeed valve has been confirmed, along with an installation date of 2018. The overspeed valve shall be scheduled for a category 5 test on or before the next annual inspection. | 9/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Battery lowering shall work. UPS is missing. Take corrective action as needed. | 7/12/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car door restrictor shall work at all floors. | 7/12/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Replace missing up-thrust roller bearings on hoistway doors. | 7/18/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | MCP, including PM records and monthly fire service test log, not being properly documented. | 7/18/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | There is no alarm on phase I fire service return. | 1/13/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. | 9/26/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Battery Lowering shall work. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually. | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | MCP - Fire Service must be tested and properly documented monthly on Log Sheet | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | 4x4 electrical box (Fire Alarm Relay) in machine room needs to have cover installed |