Inspection
Inspection Details
Equipment ID
12
12
Inspection Date
11/6/2023
11/6/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Walter Tauchert
Walter Tauchert
Relief Valve Pressure
TBD
TBD
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
19F/19R
19F/19R
External ID
f9c42e81-a6a4-48c2-ad0c-faedf7a0778f
f9c42e81-a6a4-48c2-ad0c-faedf7a0778f
Location
Des Peres City Hall
12325 Manchester Rd, Des Peres, MO
Phone: (314) 835-6100
12325 Manchester Rd, Des Peres, MO
Phone: (314) 835-6100
Owner
Attn: Des Peres
Des Peres, City of
12325 Manchester Rd, Des Peres, MO 63131
Phone: (314) 835-6111
Email: cnewgent@desperesmo.org
Des Peres, City of
12325 Manchester Rd, Des Peres, MO 63131
Phone: (314) 835-6111
Email: cnewgent@desperesmo.org
Billing
Attn: Des Peres
Des Peres, City of
12325 Manchester Rd, Des Peres, MO 63131
Phone: (314) 835-6111
Email: jlewis@desperesmo.org
Des Peres, City of
12325 Manchester Rd, Des Peres, MO 63131
Phone: (314) 835-6111
Email: jlewis@desperesmo.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency lighting shall be operational. | 2/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | No | No | All the on site documentation required by A17.1 2016 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Currently, schematics are present - please provide the MCP approved by the MO state AHJ | 12/1/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 12/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | Evacuation procedures are missing from the MCP. | 12/1/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. | 12/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency lights shall be operational. (2nd Notice) | 11/6/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car alarm bell shall be operational on main and on auxiliary power. (2nd Notice) | 11/6/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. | 12/1/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | The controller cover on the car top shall be installed. | 12/1/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The test is incomplete. The elevator went down in the middle of the test. Fire service and relief pressure still need to be tested. | 12/4/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | MCP Fire Service testing must be properly documented monthly on Log Sheet. 2025 is completely blank. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Compliant/Required MCP Documentation shall be kept in equipment room(neat/organized) including Testing Procdedures. | |
| A17.1-2016 : Elevators | 2.37 - Pressure Switch | 8.6.5.14.5 | No | No | Low pressure switch shall work as designed or be removed. Jack head is not above Tank, LPS not required and is not wired into the controller. |