Inspection
Inspection Details
Equipment ID
13348
13348
Inspection Date
10/18/2018
10/18/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Steven Perez
Steven Perez
Relief Valve Pressure
Slide
Governor Rope Pull
NA
NA
Door Closing Force
30/bi-parting freight
30/bi-parting freight
External ID
9ab64dda-7eaa-4773-abff-b1b2f30466d0
9ab64dda-7eaa-4773-abff-b1b2f30466d0
Location
Anheuser Busch- Bldg #237
1 BUSCH PL, SAINT LOUIS, MO
1 BUSCH PL, SAINT LOUIS, MO
Owner
Anheuser Busch
1 BUSCH PL, SAINT LOUIS, MO 63118-1849
1 BUSCH PL, SAINT LOUIS, MO 63118-1849
Billing
Attn: Anheuser Busch
1 BUSCH PL, SAINT LOUIS, MO 63118-1849
1 BUSCH PL, SAINT LOUIS, MO 63118-1849
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 3.8 - Top emergency exit | 1001.2(c)(12) | No | No | Repair escape hatch switch that is disabled and removed from its position. | 10/21/2019 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light inoperative. | 5/1/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm inoperative. | 5/1/2020 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Yes | No | Suspension ropes are undersized. 60 day repair/reinspection. | 12/21/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Door restrictor has been made inoperable. Re-inspection required | 11/15/2022 |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 Runby (Re-Inspect) | Yes | No | Shorten ropes 5", runby had to move finally for it to work | 11/15/2022 |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 Runby (Re-Inspect) | Yes | No | Unit only has 4 1/4" runby and it needs 6". Top final had to be moved. Re-inspection required with in 30 days. This is the second notice | 10/16/2023 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Door restrictor shall be made operable. Re-inspection required. This is the second notice | 10/16/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Door restrictor is not working. Re-inspection required, 2nd notice | 10/29/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Various floors need the fire tabs bent down | 10/9/2025 |