Inspection
Inspection Details
Equipment ID
595
595
Inspection Date
11/30/2023
11/30/2023
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Wayne Ingram
Wayne Ingram
Mechanic Name
Kyler Hyde
Kyler Hyde
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25
25
External ID
4554ab3f-9eed-41c4-8b87-b689db5892cd
4554ab3f-9eed-41c4-8b87-b689db5892cd
Location
Grove Professional Pharmacy Inc
1522 E Sunshine St, Springfield, MO
Phone: (417) 555-5555
Email: belinda@grovepharmacy.com
1522 E Sunshine St, Springfield, MO
Phone: (417) 555-5555
Email: belinda@grovepharmacy.com
Owner
Attn: Grove Professional Pharmacy Inc
Grove Professional Pharmacy Inc
1522 E Sunshine St, Springfield, MO 65804
Phone: (417) 881-2910
Email: belinda@grovepharmacy.com
Grove Professional Pharmacy Inc
1522 E Sunshine St, Springfield, MO 65804
Phone: (417) 881-2910
Email: belinda@grovepharmacy.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | alarm bell not working | 9/23/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light and bell not working | 10/20/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove storage of non-elevator related items. | 4/28/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power needs tested could not test during inspection due to interruption of services. | 4/28/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency failed to operate properly (Dials does not connect). | 4/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | No on-site documentation accessible for review / no maintenance records / no call back logs / | 4/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Scavenger pump in pit needs removed install five (5) gallon collection buckets. | 4/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Pit needs cleaned | 4/28/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Air conditions lines running through machine room installed in 2019 or 2020 needs to be removed. | 4/28/2022 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.1 Examination and Maintenance | Yes | No | Jack seals leaking | 4/29/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Machine room door lock is to be self-locking. | 4/29/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Yes | No | Out of date 2020 | 4/29/2026 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Yes | No | Post updated certificate. | 4/29/2026 |