Inspection
Inspection Details
Equipment ID
221
221
Inspection Date
12/1/2023
12/1/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James VanZant
James VanZant
Mechanic Name
Jeremiah Dugger
Jeremiah Dugger
Relief Valve Pressure
Slide
6in
6in
Governor Rope Pull
75/350
75/350
Door Closing Force
26
26
External ID
b153fe75-36f8-49ac-85c9-9b218038913c
b153fe75-36f8-49ac-85c9-9b218038913c
Location
Madison Towers
421 W MADISON ST, SPRINGFIELD, MO
Phone: (417) 866-4329
421 W MADISON ST, SPRINGFIELD, MO
Phone: (417) 866-4329
Owner
Attn: Chuck Hicks
Springfield Housing Authority
421 W Madison St, Springfield, MO 65806
Phone: (000) 000-0000
Email: chicks@hasproperties.org
Springfield Housing Authority
421 W Madison St, Springfield, MO 65806
Phone: (000) 000-0000
Email: chicks@hasproperties.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | clean car top | 1/9/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit lights are burnt out | 1/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.18 - Traction drive machines | 8.11.2.1.2(p) | Yes | No | 1/5/21 Machine bearings or worm/ring need to be repaired/replaced. VERY noisy. | 8/11/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | No | No | 1/5/21: 2.20.9.5.4 : Hoist rope retaining clip missing, car side. | 4/16/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 1/5/21: 2-way communication device shall work and give proper location (REINSPECTION REQUIRED) | 8/11/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.18 - Traction drive machines | 8.11.2.1.2(p) | Yes | No | 1/5/21 Machine bearings or worm/ring need to be repaired/replaced. VERY noisy. | 8/11/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 1/5/21: 2-way communication device shall work and give proper location (REINSPECTION REQUIRED) | 8/11/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc)(1) Wire ropes shall be replaced | Yes | Yes | UNDERSIZED/DAMAGED ROPES. | 3/30/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)7 | No | No | Replace/repair broken flex connector on governor wiring. | 5/1/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove trash/old parts from machine room. Clean as needed. | 5/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace non-functional controller cooling fans and keep controller doors closed and latched. | 5/1/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | TESTING INCOMPLETE. MUST RETURN TO COMPLETE. | 3/30/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc)(1) Wire ropes shall be replaced | Yes | Yes | UNDERSIZED/DAMAGED ROPES. | 3/30/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | TESTING INCOMPLETE. MUST RETURN TO COMPLETE. | 3/30/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall work and give proper location | 3/31/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Yes | No | Phase 1 Indicator LED @ 1st Floor not working. | 11/18/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean Pit. | 11/29/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide MCP in machine room | 2/5/2024 |