Inspection
Inspection Details
Equipment ID
6259
6259
Inspection Date
11/22/2023
11/22/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Justin Kennedy
Justin Kennedy
Relief Valve Pressure
410
410
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
19
19
External ID
f98c9288-c808-4539-b617-cb55f4bbef59
f98c9288-c808-4539-b617-cb55f4bbef59
Location
Wilson Hall
4525 DOWNS DR, SAINT JOSEPH, MO
Phone: (816) 271-4417
4525 DOWNS DR, SAINT JOSEPH, MO
Phone: (816) 271-4417
Owner
Attn: MO Western State University
MO Western State University
4525 Downs Dr, St. Joseph, MO 64507
Phone: (816) 271-4417
Email: phyplant@missouriwestern.edu
MO Western State University
4525 Downs Dr, St. Joseph, MO 64507
Phone: (816) 271-4417
Email: phyplant@missouriwestern.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | No | No | Emergency light and bell do not operate. | 7/8/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside machine room | 3/2/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove oil and debris from machine room floor. | 3/2/2021 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | No | No | Replace or repair hydraulic pumping unit that is leaking oil onto machine room floor. | 3/2/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate inside the machine room | 4/7/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | Wiring diagrams shall be kept in the machine room | 4/7/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Post In Case of Fire signage next to corridor call station at each landing | 4/7/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Test and log firefighter operation monthly | 4/7/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | No machine room lighting. Repair or replace light fixture. | 11/25/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not operate | 11/26/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lighting burned out | 11/25/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | KEEP MACHINE ROOM ACCESSABLE ( BUILDING IS STORING EQUIPMENT IN FRONT OF MACHINE ROON DOOR ) | 11/25/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | REMOVE ALL BUILDING ITEMS FROM MECHANICAL ROOM DOOR TO THE ELEVATOR MACHINE ROOM DOOR. THIS MUST BE KEPT FREE AND CLEAN SO WE HAVE SAFE PASSAGE TO GET TO THE ELEVATOR MACHINE ROOM DOOR . ( SAME PROMLEM AS LAST YEARS INSPECTION ) |