Inspection
Inspection Details
Equipment ID
80
80
Inspection Date
11/21/2023
11/21/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Thomas Nash
Thomas Nash
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
7d39400c-31c8-42b0-a71c-58d143ee68ff
7d39400c-31c8-42b0-a71c-58d143ee68ff
Location
Mosaic Medical Center-Maryville
2016 S Main St, Maryville, MO
Phone: (660) 562-2600
2016 S Main St, Maryville, MO
Phone: (660) 562-2600
Owner
Attn: Gary Thompson
Mosaic Medical Center-Maryville
2016 S Main St, Maryville, MO 64468
Phone: (660) 562-7939
Email: Gary.Thompson@mymlc.com
Mosaic Medical Center-Maryville
2016 S Main St, Maryville, MO 64468
Phone: (660) 562-7939
Email: Gary.Thompson@mymlc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 9/30/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | No | No | Provide lighting in machine room. Existing feed for machine lights has no electrical power | 2/22/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | No | No | Label machine room equipment with identification that corresponds to identification inside the elevator and the car crosshead. | 11/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Identify inside of hoistway doors with a numeral corresponding to landing floor. | 11/16/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Perform emergency standby operation with an inspector present. | 8/24/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide "Elevator Emergency Power" signal at the lobby of the designated landing. | 9/8/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 11/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 (Re-Inspection) | Yes | No | Replace pit sprinkler head with sidewall sprinkler head located within 24 inches of pit floor | 11/21/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | Yes | No | Test emergency power operation with inspector present | 11/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | REPAIR PIT LIGHTING | 10/21/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.8 - Door closing force | 2.13.4.2.3 | Yes | No | FRONT DOOR TORQUE IS >30lbs | 1/16/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.5 - Normal terminal stopping device | 2.26.2 | Yes | No | DOWN LIMIT DID NOT WORK | 1/16/2026 |