Inspection
Inspection Details
Equipment ID
10603
10603
Inspection Date
10/3/2017
10/3/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
F25/R freight doors
F25/R freight doors
External ID
Location
Anheuser Busch- Bldg #202
One Busch Place, St. Louis, MO
Phone: (314) 577-2667
One Busch Place, St. Louis, MO
Phone: (314) 577-2667
Owner
Anheuser Busch
One Busch Place, St. Louis, MO 63118
One Busch Place, St. Louis, MO 63118
Billing
Attn: Anheuser Busch
One Busch Place, , MO 63118
One Busch Place, , MO 63118
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Rear alarm bell button does not work | 10/15/2021 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Yes | No | Suspension ropes are undersized and stretched. Reinspect in 120 days | 10/15/2021 |
| A17.1-1996 : Elevators | 3.10 - Hoistway construction | 1001.2(c)(16) | No | No | Patch holes by car doors inside hoistway | 9/19/2025 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 1001.2(a)(12) | No | No | Cover hole on top of car with exposed wires | 9/19/2025 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Yes | No | Suspension ropes are undersized and stretched. Reinspect in 90 days | 5/19/2022 |
| A17.1-1996 : Elevators | 3.10 - Hoistway construction | 1001.2(c)(16) | No | No | Patch holes by car doors inside hoistway | 9/19/2025 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 1001.2(a)(12) | No | No | Cover hole on top of car with exposed wires | 9/19/2025 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 212 | Yes | No | Suspension ropes are undersized & stretched. Re-inspection required | 10/21/2022 |
| A17.1-1996 : Elevators | 3.10 - Hoistway construction | 100 | No | No | Patch holes by car doors inside hoistway | 9/19/2025 |
| A17.1-1996 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 102.1 | No | No | Cover hole on top of car top with exposed wires | 9/19/2025 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Car door restrictor is not working. Re-inspection required | 10/2/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | The sill plate on the 2nd floor shall be replaced or repaired, there is only one anchor securing it to the floor and it is loose. | 9/19/2025 |