Inspection
Inspection Details
Equipment ID
19818
19818
Inspection Date
12/6/2023
12/6/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Dennis Smith
Dennis Smith
Relief Valve Pressure
420
420
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
20
20
External ID
aa2652a3-9b79-4180-aaeb-493db197ce45
aa2652a3-9b79-4180-aaeb-493db197ce45
Location
Nodaway County Admin
403 N Market St, Maryville, MO
Phone: (660) 582-5541
403 N Market St, Maryville, MO
Phone: (660) 582-5541
Owner
Attn: Nodaway County
Nodaway County
403 N Market St, Maryville, MO 64468
Phone: (660) 582-2251
Email: nodclerk@gmail.com
Nodaway County
403 N Market St, Maryville, MO 64468
Phone: (660) 582-2251
Email: nodclerk@gmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not operate. | 4/18/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate. | 11/17/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 11/16/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside machine | 1/28/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | No | No | Post code data plate on controller or disconnect | 1/28/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | No | No | Post code data plate on controller or disconnect. "ASME A17.1 2004" | 6/1/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 2.29.2 | No | No | Identify inside of hoistway doors with a numeral | 6/1/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not function | 11/29/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | No | No | Post In Case of Fire pictograph signage at landings next to corridor call station. | 6/1/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside the machine room | 6/1/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | No | No | Car operating station does not have a Phase 2 Operation Panel. | 11/29/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | No | No | Post code data plate on controller or disconnect. "ASME A17.1 2004" | 3/16/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 2.29.2 | No | No | Label inside of hoistway door with a numeral no less than 4 inches in height | 3/16/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not operate | 4/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 2.12.7 | No | No | Provide hoistway access switch at the top landing. | 3/16/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | Yes | No | Fire service panel on the car operating panel is not behind a locked cabinet | 4/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No state operating certificate displayed | 3/16/2023 |