Inspection
Inspection Details
Equipment ID
7065
7065
Inspection Date
11/13/2023
11/13/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Jeffrey Miller
Jeffrey Miller
Relief Valve Pressure
300
300
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
22
22
External ID
55390bc2-c26d-4b82-abc7-652eb9ab9dc9
55390bc2-c26d-4b82-abc7-652eb9ab9dc9
Location
Cori Manor Nursing
560 Corisande Hills Rd, Fenton, MO
Phone: (636) 343-2282
560 Corisande Hills Rd, Fenton, MO
Phone: (636) 343-2282
Owner
Attn: Cori Manor Health Care & Rehab Ctr
Cori Manor Health Care & Rehab Ctr
560 Corisande Hills Rd, Fenton, MO 63026
Phone: (636) 343-2258 Ext: 647
Email: virgil.thomas@hma-usa.com
Cori Manor Health Care & Rehab Ctr
560 Corisande Hills Rd, Fenton, MO 63026
Phone: (636) 343-2258 Ext: 647
Email: virgil.thomas@hma-usa.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Make repairs to the T-cable hanger under the elevator. | 12/5/2019 |
| conversion | conversion | n/a | No | No | Make repairs to guide shoes on the bottom of the elevator for proper operation. | 12/5/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Top of car inspection operation shall conform to 2.26.1.4.1 and the following: A stop switch shall be permanently installed and located on the car top and readily accessible to a person while standing at the hoistway entrance normally used for access to the car top. The car top stop switch does not work and shall be repaired. | 12/5/2019 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)1 | No | No | The elevator shutdown during inspection. The relief pressure shall be tested. | 12/5/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. | 12/5/2019 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Properly secure the traveling cable to the bottom of the car and properly secure and protect the cable where it goes through the cab platform. | 12/5/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency lighting shall be operational. | 1/28/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency alarm bell shall be operational. | 1/28/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 2/14/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 12/29/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emmergency communications/phone in car is still not working. | 2/23/2026 |