Inspection
Inspection Details
Equipment ID
17626
17626
Inspection Date
11/16/2023
11/16/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Brian Wirtz
Brian Wirtz
Relief Valve Pressure
490
490
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
18
18
External ID
019ee3e4-5e56-40a4-813e-071e041220c4
019ee3e4-5e56-40a4-813e-071e041220c4
Location
Field School Lofts
4466 Olive St, St. Louis, MO
Phone: (314) 680-4544
4466 Olive St, St. Louis, MO
Phone: (314) 680-4544
Owner
Attn: Field School Lofts c/o Garcia Property Management
Field School Lofts c/o Garcia Property Management
3537 S Kingshighway Blvd, St. Louis, MO 63139
Phone: (314) 353-0336 Ext: 408
Email: miguel@garciaproperties.com
Field School Lofts c/o Garcia Property Management
3537 S Kingshighway Blvd, St. Louis, MO 63139
Phone: (314) 353-0336 Ext: 408
Email: miguel@garciaproperties.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | Yes | No | Make door restrictor operational. | 10/18/2018 |
| A17.1-1996 : Elevators | 3.3 - Top-of-car operating device | 1001.2(c)(3) | No | No | Make car top run station operational. - Reinspection Required | 10/25/2018 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Red Tag) | Yes | No | In cab emergency telephone shall work. | 10/18/2018 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Existing cab emergency telephone shall work with 24/7 support. | 10/24/2018 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 10/25/2018 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light inoperative. | 11/24/2020 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Service fire extinguisher. | 11/1/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light does not work. | 6/16/2021 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Fire extinguisher is expired | 11/1/2022 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the state operating certificate shall be displayed in the elevator machine room | 11/1/2022 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | No | No | Pit light bulbs shall be guarded | 11/1/2022 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | No | No | Smoke device in pit needs to be remounted on electrical box | 11/1/2022 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | Yes | No | Elevator shall be removed from phase I emergecny recall by keying phase I switch to RESET then OFF. Unit had to be reset from controller to return to automatic operation. | 4/16/2026 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit shall be kept clean. Remove excess debris, excessive dust, and oil. | 4/16/2026 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 100.3d | No | No | Machine lighting shall be repaired, 1 or more bulbs not working. | 4/16/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Fire service testing must be documented montly. | 4/16/2026 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and realted on-site documentation shal be provided in the machine room. No MCP documentation predent for 2022, 2023, and 2024. | 4/16/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | Yes | No | Elevator shall be removed from phase I emergecny recall by keying phase I switch to RESET then OFF. Unit had to be reset from controller to return to automatic operation. | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit shall be kept clean. Remove excess debris, excessive dust, and oil. | |
| A17.1-1996 : Elevators | 2.4 - Machine space | 100.3d | No | No | Machine lighting shall be repaired, 1 or more bulbs not working. | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Fire service testing must be documented montly. | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and realted on-site documentation shal be provided in the machine room. No MCP documentation predent for 2022, 2023, and 2024. |