Inspection
Inspection Details
Equipment ID
20797
20797
Inspection Date
9/11/2018
9/11/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Thomas Droege
Thomas Droege
Relief Valve Pressure
Slide
Governor Rope Pull
N/A
N/A
Door Closing Force
21
21
External ID
025ae49e-2b79-4511-9b11-60e83e2fb121
025ae49e-2b79-4511-9b11-60e83e2fb121
Location
Chaminade College Prep School
425 S LINDBERGH BLVD, SAINT LOUIS, MO
425 S LINDBERGH BLVD, SAINT LOUIS, MO
Owner
Chaminade College Prep School
425 S LINDBERGH BLVD, SAINT LOUIS, MO 63131-2729
425 S LINDBERGH BLVD, SAINT LOUIS, MO 63131-2729
Billing
Attn: Chaminade College Prep School
425 S LINDBERGH BLVD, SAINT LOUIS, MO 63131-2729
425 S LINDBERGH BLVD, SAINT LOUIS, MO 63131-2729
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Car emergency lighting shall work. | 9/5/2019 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | Emergency lights shall work. | 9/5/2019 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Provide max counterweight sign in the pit. | 9/5/2019 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 8/28/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | x | The emergency power jewel/indicator shall be operational to indicate unit has transferred to emergency power. Emergency power shall be tested and the emergency power jewel shall be operational. | 11/7/2022 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Emergency power operation not working. Generator would not transfer power. | 7/1/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 7/1/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | x | The in car emergency light shall be operational. | 7/1/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.4 Means for Manual Release | x | The manual brake release was not able to be tested. Testing procedures shall be kept on-site. | 7/1/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | x | Fire stops are missing on both hoistway doors at 1st and 2nd floors. | 7/1/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 7/1/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | x | 2-way communication device shall work. Red Tag Issued, phone did not work on 7/5/23 inspection. | 8/21/2024 |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.4 Means for Manual Release | x | Emergency brake release handle shall work. | 8/21/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current state operating permit shall be obtained and displayed in the equipment room. | 8/21/2024 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.4 Means for Manual Release | x | Emergency brake release handle shall work. Violation still remains as of 8/21/24. | 10/25/2024 |