Inspection
Inspection Details
Equipment ID
6364
6364
Inspection Date
12/8/2023
12/8/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Scott Bonham
Scott Bonham
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
65828703-c8d4-4a34-8713-c6fe76f6f5bb
65828703-c8d4-4a34-8713-c6fe76f6f5bb
Location
Corby Building
422 Felix St, St. Joseph, MO
Phone: (816) 233-4600
422 Felix St, St. Joseph, MO
Phone: (816) 233-4600
Owner
Attn: Corby Senior Living
Corby Senior Living
PO Box 374, Pico Rivera, CA 90660
Phone: (000) 000-0000
Email: cburris@corbyplace.com
Corby Senior Living
PO Box 374, Pico Rivera, CA 90660
Phone: (000) 000-0000
Email: cburris@corbyplace.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Emergency light and bell do not operate. | 12/3/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Need to post fire service instructions inside the elevator | 12/3/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Need to remove debris from machine room floor. | 8/25/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need to post emergency evacuation of passengers form inside machine room. | 8/25/2020 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace rouged and undersized governor rope. | 7/16/2021 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Car safeties do not stop the elevator. Slide is 56 inches and exceeds allowed limits | 7/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Install seal on machine brake spring tension adjustment nut. | 7/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace worn traction sheave liners | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace broken hoist rope shackle springs on the car and counterweight connections | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2.5 Rope Tension (Re-Inspect) | Yes | No | Equalize hoist rope tension | 12/8/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Lobby dial position indicator is not operating and needs repair. | 12/7/2023 |