Inspection
Inspection Details
Equipment ID
11665
11665
Inspection Date
11/14/2023
11/14/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Thadeus Haston
Thadeus Haston
Relief Valve Pressure
n/a
n/a
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
n/a
n/a
External ID
4d2d8bf8-8101-4431-9848-ca83fe3e1b73
4d2d8bf8-8101-4431-9848-ca83fe3e1b73
Location
Arrowhead Stadium
1 Arrowhead Dr, Kansas City, MO
Phone: (816) 921-3600
1 Arrowhead Dr, Kansas City, MO
Phone: (816) 921-3600
Owner
Attn: Jackson County Sports Authority
Jackson County Sports Authority
1 Arrowhead Dr, Kansas City, MO 64129
Phone: (816) 920-4962
Email: krutter@chiefs.nfl.com
Jackson County Sports Authority
1 Arrowhead Dr, Kansas City, MO 64129
Phone: (816) 920-4962
Email: krutter@chiefs.nfl.com
Billing
Attn: Jackson County Sports Authority
Jackson County Sports Authority
1 Arrowhead Dr, Kansas City, MO 64129
Phone: (816) 920-4962
Email: tidel@chiefs.nfl.com
Jackson County Sports Authority
1 Arrowhead Dr, Kansas City, MO 64129
Phone: (816) 920-4962
Email: tidel@chiefs.nfl.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(j) | No | No | Machine room fire extinguisher inspection tag is from 2019, it is to be inspected and tagged annually. | 7/28/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(c) | No | No | The Maintenance Control Program On-Site documents are not in the machine room. | 7/28/2025 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. | 7/28/2025 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. The certificate on display in the machine room is from 2016. | 7/28/2025 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | Yes | No | Emergency lights did not come on, repair emergency light system. | 5/30/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | A Maintenance Control Program (MCP) for each unit shall be provided by the person and/or firm maintaining the equipment and shall be viewable onsite by elevator personnel at all times. | 7/28/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(c)(2) | No | No | A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room. | 7/28/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | Did not have a written record of the maintenance performed on this elevator in the machine room. | 7/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone continues to ring even after answering service answers the phone, the ringing makes two way conversation next to impossible | 11/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Clean up rusted pit equipment and prevent accumulation of groundwater in the pit (2.2.2.3) | 7/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone did not work | 6/25/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | clean up and protect rusted pit equipment |