Inspection
Inspection Details
Equipment ID
22144
22144
Inspection Date
12/6/2023
12/6/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Bradley Tramel
Bradley Tramel
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
52847323-479d-48c8-a6e4-d9dae30ff80e
52847323-479d-48c8-a6e4-d9dae30ff80e
Location
Drury Inn & Suites St. Louis Brentwood
8700 Eager Rd, St. Louis, MO
Phone: (314) 968-3704
Fax: (314) 961-6220
Email: dis.btwd.164.gm@druryhotels.com
8700 Eager Rd, St. Louis, MO
Phone: (314) 968-3704
Fax: (314) 961-6220
Email: dis.btwd.164.gm@druryhotels.com
Owner
Attn: Drury Development Corporation
Drury Development Corporation
13075 Manchester Rd, Ste 200, St. Louis, MO 63131
Phone: (314) 968-3704 Ext: 7070
Email: pat.travers@druryhotels.com
Drury Development Corporation
13075 Manchester Rd, Ste 200, St. Louis, MO 63131
Phone: (314) 968-3704 Ext: 7070
Email: pat.travers@druryhotels.com
Billing
Attn: Drury Inn & Suites St. Louis Brentwood
Drury Inn & Suites St. Louis Brentwood
8700 Eager Rd, Brentwood, MO 63144
Phone: (314) 968-3704 Ext: 7070
Email: p0164@druryhotels.com
Drury Inn & Suites St. Louis Brentwood
8700 Eager Rd, Brentwood, MO 63144
Phone: (314) 968-3704 Ext: 7070
Email: p0164@druryhotels.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide missing on site documents for maintenance control program. | 10/20/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate. | 10/20/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.3.3.3 Runby & Clearances After Reroping or shortening | Yes | No | Provide completed runby sign in pit. | 12/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.4.10 Emegency Operation and Signaling Devices | Yes | No | The seismic device on the counterweight did not initiate when activated. Repair device to operate when activated. | 4/25/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) | Yes | No | No audible alarm when fire service is initiated. Re-inspection required | 9/25/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car door restrictor is not working. Re-inspection required | 12/6/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire service Phase 2 is not working. Re-inspection required within 10 days | 12/6/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) | Yes | No | No audible alarm when service is initiated. Re-inspection required | 12/6/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The car safeties shall be set, and overspeed switch tested before the inspection is completed. | 9/17/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 9/17/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.4.10 Emegency Operation and Signaling Devices | Yes | No | The sounding buzzer for seismic activation failed to sound when activated. Repair/reprogram buzzer to activate as required. | 9/17/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.18 | Yes | Yes | Upon performing the required five year full load, the elevator safety governor overspeed switch failed to activate within the required tolerance.Repair or replacement of the governor is required and a reinspection shall be performed before the elevator can be returned to service. | 9/17/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The car safeties shall be set, and overspeed switch tested before the inspection is completed | 9/17/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. | 9/17/2024 |