Inspection
Inspection Details
Equipment ID
10255
10255
Inspection Date
12/7/2023
12/7/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
27
27
External ID
53b84a40-c3c6-4bc5-abc1-c0befec3e8bb
53b84a40-c3c6-4bc5-abc1-c0befec3e8bb
Location
Metropolitan Square
211 N Broadway, St. Louis, MO
Phone: (314) 436-1212
211 N Broadway, St. Louis, MO
Phone: (314) 436-1212
Owner
Attn: Metropolitan Square LLC
Metropolitan Square LLC
211 N Broadway, St. Louis, MO 63102
Phone: (314) 982-1400 Ext: 4662
Email: sam.mauer@am.jll.com
Metropolitan Square LLC
211 N Broadway, St. Louis, MO 63102
Phone: (314) 982-1400 Ext: 4662
Email: sam.mauer@am.jll.com
Billing
Attn: Jones Lang LaSalle
Jones Lang LaSalle
211 N Broadway, Ste 1290, St. Louis, MO 63102
Phone: (314) 436-1212
Email: melissa.walker@jll.com
Jones Lang LaSalle
211 N Broadway, Ste 1290, St. Louis, MO 63102
Phone: (314) 436-1212
Email: melissa.walker@jll.com
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Suspension ropes are below minimum diameter. Replace within 30 days. | 11/11/2019 | |
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency bell is not working. Re-inspection required | 7/8/2022 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Test incomplete, need to perform 125% brake test. Re-inspection required | 7/8/2022 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Test incomplete, need to perform full load buffer test for car & counterweight. Re-inspection required | 7/8/2022 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Test incomplete, need to perform full load safety set. Re-inspection required | 7/8/2022 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Test incomplete, need to test spin governor. Re-inspection required | 7/8/2022 | |
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Emergency power operation needs to be tested | 12/7/2023 | |
MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | x | Repair inoperative Phase l fire recall visiual indicator | 12/7/2023 | |
MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Repair lights above hoist machine to provide required illumination | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | Repair inoperative emergency Lights | 12/7/2023 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2.5 Rope Tension (Re-Inspect) | x | Replace broken shackel springs on car and counterweight ends | 12/7/2023 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2.5 Rope Tension (Re-Inspect) | x | Replase missmatched shackle spring on counterweight | 12/7/2023 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Replace defective right top post roller on counterweights | |||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current operating certificate shall be displayed in the machine room | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | Elevator cab emergency lights do not work, need repaired. Re-inspection required | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Suspension ropes have broken shackle springs on the car & counterweights, need to replace shackle springs | |||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Need to test elevator for operation on emergency power. Re-inspection required |