Inspection
Inspection Details
Equipment ID
10242
10242
Inspection Date
12/4/2023
12/4/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
26
26
External ID
e6b79409-32bd-44b6-8dd1-56d493d5d030
e6b79409-32bd-44b6-8dd1-56d493d5d030
Location
Metropolitan Square
211 N Broadway, St. Louis, MO
Phone: (314) 436-1212
211 N Broadway, St. Louis, MO
Phone: (314) 436-1212
Owner
Attn: Metropolitan Square LLC
Metropolitan Square LLC
211 N Broadway, St. Louis, MO 63102
Phone: (314) 982-1400 Ext: 4662
Email: sam.mauer@am.jll.com
Metropolitan Square LLC
211 N Broadway, St. Louis, MO 63102
Phone: (314) 982-1400 Ext: 4662
Email: sam.mauer@am.jll.com
Billing
Attn: Jones Lang LaSalle
Jones Lang LaSalle
211 N Broadway, Ste 1290, St. Louis, MO 63102
Phone: (314) 436-1212
Email: melissa.walker@jll.com
Jones Lang LaSalle
211 N Broadway, Ste 1290, St. Louis, MO 63102
Phone: (314) 436-1212
Email: melissa.walker@jll.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Governor rope must be replaced. Re-inspection required | 1/18/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Two shackle springs are broken, need to be replaced | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light not working. Re-inspection required | 1/18/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Counterweights need to be tested. Re-inspection required | 1/18/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire service needs to be tested. Re-inspection required | 1/18/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Has not completed the Category 5 Inspection for 2022. The following issues are unresolved: 1 - Counterweight buffer has not been tested. Unable to complete due to seismic construction. 2 - Car buffer has not been tested. Unable to complete due to seismic construction. 3 - The governor rope has been damaged and shall be replaced. 4 - Fireman’s emergency service phase I and II have not been tested. Unable to reinspect due to being out of service for repair. | 5/9/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | Unable to test door pressure due damage incurred from striking the seismic bolts in the hoistway. | 9/22/2025 |
| A17.1-2016 : Elevators | 3.14 - Hoistway clearances | 2.4 | No | No | Seismic strengthening of the elevator hoistway has been performed. This has resulted in a number of issues listed. 1- No alteration permit has been applied for. 2-The elevator car has struck the seismic bolts that have been added to the hoistway. Clearances shall be checked. 3-Elevator car door header has been damaged by striking seismic bolts in the hoistway. 4-The seismic contractor (Paric) shall finish the work in the hoistway and certify its completion before the elevator can be returned to service. Numerous nuts were observed that were not properly secured and could potential cause damage to the elevator and the occupants inside. | 9/22/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire service phase 1 and 2 and emergency generator power operation still needs to be tested to complete 5 year inspection | 12/4/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Hoist rope shackle spring is broken. Replace same | 9/22/2025 |
| A17.1-2016 : Elevators | 3.14 - Hoistway clearances | 2.4 | No | No | Seismic strengthening of the elevator hoistway has been performed. This has resulted in a number of issues listed. 1- No alteration permit has been applied for. 2-The elevator car has struck the seismic bolts that have been added to the hoistway. Clearances shall be checked. 3-Elevator car door header has been damaged by striking seismic bolts in the hoistway. 4-The seismic contractor (Paric) shall finish the work in the hoistway and certify its completion before the elevator can be returned to service. Numerous nuts were observed that were not properly secured and could potential cause damage to the elevator and the occupants inside. | 9/22/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Down final limit switch roller is damaged and needs replacing | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Suspension rope shackle spring is broken in machine room, needs to be replaced | 9/22/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test elevator for operation on emergency power. Re-inspection required | 8/21/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone is not working on battery backup, needs repaired. Re-inspection required | 8/21/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current operating certificate shall be displayed in the machine room | 9/22/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | FEO Phase 2 Bezel shall be labeled. | 9/22/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Call Cancel button shall be labeled | 11/18/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency Power needs to be tested - Test not completed | 9/20/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | Yes | No | Seismic strengthening of the elevator hoistway has been performed. No alteration permit was obtained. Numerous nuts on west wall are loose and could potential cause damage to the elevator/occupants. | 9/20/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Numerous nuts on west wall are loose and could potential cause damage to the elevator/occupants. | 11/18/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | FEO Phase 2 Bezel shall be labeled. | 11/18/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current Operating Certificate shall be displayed in the machine room | 11/18/2025 |