Inspection
Inspection Details
Equipment ID
4850
4850
Inspection Date
12/12/2023
12/12/2023
Inspection Type
Alteration
Alteration
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Joel Vorbeck
Joel Vorbeck
Relief Valve Pressure
n/a
n/a
Slide
6"
6"
Governor Rope Pull
n/a
n/a
Door Closing Force
n/a
n/a
External ID
72450433-881b-4c7d-9004-4cefc7b95cdb
72450433-881b-4c7d-9004-4cefc7b95cdb
Location
Temple Heights Manor I
5420 Blue Ridge Cut Off, Raytown, MO
Phone: (816) 358-9537
5420 Blue Ridge Cut Off, Raytown, MO
Phone: (816) 358-9537
Owner
Attn: Temple Heights
Temple Heights Manor dba Temple Heights Manor I
5420 Blue Ridge Cut Off, Raytown, MO 64133
Phone: (660) 864-0529
Email: manager@templeheightsmanor.com
Temple Heights Manor dba Temple Heights Manor I
5420 Blue Ridge Cut Off, Raytown, MO 64133
Phone: (660) 864-0529
Email: manager@templeheightsmanor.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.17 - Drive machine brake | 207.2b | Yes | Yes | the brake stopped and held but the ropes slid over the dirve sheave and the car went past the down finial onto the buffer | 6/18/2021 |
| A17.1-2016 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(i) | No | No | The machine room air conditioner does not seem to be working correctly, the temperature in the room was much higher than the setting on the thermostat | 6/18/2021 |
| A17.1-2016 : Elevators | 1.4 - Sills and car floor | 2.11.10.2 | No | No | the lobby lights at each landing were not working at the time of the test | 6/18/2021 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(c)(2) | No | No | A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room. | 6/18/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | emergency light did not com on, alarm bell worked | 1/4/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone hangs up before connecting to operator, repair and retest | 4/5/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post a new copy of the state operating certificate in the machine room every year | 4/5/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | monthly fire service test log is to be posted in the machine room | 4/5/2022 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | machine room air conditioning unit does not appear to be keeping the room cool verify proper operation of the air conditioning unit to keep room at the temperatures required by the controller manufacturer | 12/20/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate in the machine room expired in 2012, update annually with a new copy when received from the state | 12/20/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | could not complete the 5 year weight test since elevator #2 was Red tagged out of service, complete 5 year weight test once both elevators are back in service | 12/12/2023 |