Inspection
Inspection Details
Equipment ID
23376
23376
Inspection Date
12/5/2023
12/5/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
25
25
External ID
a01149df-b294-4ec1-a5fc-8f11833ad570
a01149df-b294-4ec1-a5fc-8f11833ad570
Location
University of St Louis Grand Hall
3605 Laclede Ave, St. Louis, MO
Phone: (000) 000-0000
3605 Laclede Ave, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: Barth Breneman
St. Louis University
3545 Lindell Blvd, 2nd Fl, St. Louis, MO 63103
Phone: (314) 977-2966
Email: barth.breneman@slu.edu
St. Louis University
3545 Lindell Blvd, 2nd Fl, St. Louis, MO 63103
Phone: (314) 977-2966
Email: barth.breneman@slu.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Test cab two way communitcation | 7/16/2020 |
| conversion | conversion | n/a | No | No | Test recall from fire command center switch | 7/16/2020 |
| conversion | conversion | n/a | No | No | Relocate all elevator lobby smoke detectors further that 2 ft from car door | 7/16/2020 |
| conversion | conversion | n/a | No | No | Extend pit ladder to the required 48 inch height above access sill | 7/16/2020 |
| conversion | conversion | n/a | No | No | Reduce counterweight runby to the pit posted demension | 7/16/2020 |
| conversion | conversion | n/a | No | No | Plug all hoistway to machine room penetrations | 7/16/2020 |
| conversion | conversion | n/a | No | No | Hoistway access switches inoperative | 7/16/2020 |
| conversion | conversion | conversion - reinspect | Yes | No | Install all corridor call station pictographs. | 7/23/2018 |
| conversion | conversion | n/a | No | No | Mark floor numbers on corresponding hoistway doors, car side | 7/16/2020 |
| conversion | conversion | n/a | No | No | Install all hoistway duct covers including any for car top | 7/16/2020 |
| conversion | conversion | n/a | No | No | Install 2nd pit stop switch 47 in from pit floor | 7/16/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.2 - Stop switches | 8.11.2.1.1(b) (Re-Inspection) | No | No | In car stop switch shall be overridden when car is in flight on Phase 1 Fire Service. Reinspection Required. | 7/16/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.2.7 | Yes | No | mergency power must be tested. Re-inspection required | 12/17/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.27 | Yes | No | Need to perform the required Cat 1 emergency generator testing to complete the annual testing. Re-inspection required | 7/30/2025 |