Inspection
Inspection Details
Equipment ID
13090
13090
Inspection Date
12/7/2023
12/7/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Jake Brennan
Jake Brennan
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
22F/28R
22F/28R
External ID
ae95f562-e942-4de3-b793-7ef073cd2d5b
ae95f562-e942-4de3-b793-7ef073cd2d5b
Location
St. Louis City Justice Center
200 S Tucker Blvd, St. Louis, MO
Phone: (314) 621-5848
200 S Tucker Blvd, St. Louis, MO
Phone: (314) 621-5848
Owner
Attn: Minyon Frazier-Foluke, Administrative Coordinator
St. Louis City Justice Center
200 S Tucker Blvd, St. Louis, MO 63102
Phone: (314) 621-5848
Email: frazier-folukem@stlouis-mo.gov
St. Louis City Justice Center
200 S Tucker Blvd, St. Louis, MO 63102
Phone: (314) 621-5848
Email: frazier-folukem@stlouis-mo.gov
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | No current state certificate posted. | 7/8/2018 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certiicate in machine room | 3/18/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a current MO state operating certificate. | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide a code compliant MCP including on-site documents. | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Standby power operation of the elevators shall be tested. | 4/8/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Properly display current state operating certificate in the machine room. | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures and monthly fire service testing records are missing. (This item is for notification purposes for future violation in 2022) | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way emergency communication shall be operational. | 12/5/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work with and without main power. | 11/19/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power annually. Note: Elevator failed to operate on emergency generator. | 11/19/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. 2023 documentation is blank and no fire service logs present. | |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Machine room shall have proper fire extinguisher and shall have current monthly/annual test tags. | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work with and without main power. (2nd Notice) This violation must be corrected immediately. | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power annually. | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. |