Inspection
Inspection Details
Equipment ID
15024
15024
Inspection Date
12/13/2023
12/13/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
8dd3cebc-ac53-48c6-83a5-0b74cc5a26ff
8dd3cebc-ac53-48c6-83a5-0b74cc5a26ff
Location
Mosaic Life Care
5325 Faraon St, St. Joseph, MO
Phone: (816) 271-6000
5325 Faraon St, St. Joseph, MO
Phone: (816) 271-6000
Owner
Attn: Bradley Connell
Mosaic Life Care
5325 Faraon St, St. Joseph, MO 64506
Phone: (816) 271-7539
Alt Phone: (816) 271-8876
Email: Bradley.Connell@mymlc.com
Mosaic Life Care
5325 Faraon St, St. Joseph, MO 64506
Phone: (816) 271-7539
Alt Phone: (816) 271-8876
Email: Bradley.Connell@mymlc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Test and log firefighter operation monthly | 11/17/2020 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(b)(4) | No | No | Post emergency evacuation of passengers procedure inside machine room | 11/17/2020 |
| A17.1-1996 : Elevators | 1.8 - Door closing force | 1001.2(a)(8) | Yes | No | Door pressure exceeds 30# | 12/8/2021 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light does not operate | 12/8/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not operate | 12/8/2021 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.8 Switch Keys | No | No | Install FEO-K1 keyswitches. All elevators in the same building shall have firefighter keyswitches operated by the same key | 10/24/2022 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Test operation of elevator on emergency power with an inspector present | 12/8/2021 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | In car firefighter keyswitch does not disable car calls or door close operation when keyed to the HOLD position | 11/29/2022 |
| A17.1-2016 : Elevators | 1.8 - Door closing force | 8.6.4.19.8 | Yes | No | Door force exceeds 30# | 11/29/2022 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Test operation of elevator on emergency power | 11/29/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | MRL not up to date | 2/1/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 2/1/2024 |
| A17.1-2016 : Elevators | 1.8 - Door closing force | 8.6.4.19.8 | Yes | No | Door force exceeds 30# | 10/24/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Test emergency power operation | 12/13/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 1/5/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | The emergency power was not tested. | 11/13/2024 |