Inspection
Inspection Details
Equipment ID
25087
25087
Inspection Date
12/14/2023
12/14/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Joseph Jensen
Joseph Jensen
Mechanic Name
Michael Barnhart
Michael Barnhart
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
20
20
External ID
1e345926-3a35-4068-829e-5dac84c009f3
1e345926-3a35-4068-829e-5dac84c009f3
Location
American Electric
302 N 3rd St, St. Joseph, MO
Phone: (913) 642-6000
302 N 3rd St, St. Joseph, MO
Phone: (913) 642-6000
Owner
Attn: Wes Grammer
302 North 3rd Street, LLC
PO Box 22876, Kansas City, MO 64113
Phone: (816) 867-6452
Email: haley@smg-kc.com
302 North 3rd Street, LLC
PO Box 22876, Kansas City, MO 64113
Phone: (816) 867-6452
Email: haley@smg-kc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.4 - Sills and car floor | 8.10.2.2.1(d) | No | No | car floor not installed | 12/7/2021 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emg standby power nt tested | 12/7/2021 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3 | Yes | Yes | fire int. devices not tested | 12/7/2021 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.10.2.2.1(o) | No | No | in case of fire signage not displayed | 12/7/2021 |
| A17.1-2016 : Elevators | 3.11 - Hoistway smoke control | 2.1.4 | No | No | smoke damper not tested | 12/7/2021 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 2.18.6 | Yes | No | gov pull thru not tested | 12/7/2021 |
| A17.1-2016 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 8.10.2.2.5(j) | Yes | Yes | didnt test car safties | 12/7/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certificate in machine room | 2/22/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 2/6/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency light did not come on, repair emergency light | 3/26/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | No | No | Instal cover on 4x4 junction box top of hoistway below the disconnect and at bottom of the hoistway next to the divider beam | 3/26/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.3.4 | Yes | Yes | Failed the 125% brake test, adjust or replace brake depending on the type of brake. Unit is red tagged until repair has been reinspected | 3/26/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency light did no come on | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | No | No | install cover on 4x4 Junction box top of hoistway below the disconnect and at bottom of hoistway next to the divider beam |