Inspection
Inspection Details
Equipment ID
11440
11440
Inspection Date
9/27/2018
9/27/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Vincent Daus
Vincent Daus
Mechanic Name
Alex Brinkman
Alex Brinkman
Relief Valve Pressure
Slide
Governor Rope Pull
42"/NA
42"/NA
Door Closing Force
15
15
External ID
ddcddaa1-8fdd-4983-ad28-0c2a0d8edaee
ddcddaa1-8fdd-4983-ad28-0c2a0d8edaee
Location
ABC Condominium-Aberdeen #20
20 N KINGSHIGHWAY BLVD, SAINT LOUIS, MO
20 N KINGSHIGHWAY BLVD, SAINT LOUIS, MO
Owner
Attn: UNK
ABC Condo Association c/o Rafco Properties
7700 Forsyth Blvd, Ste 100, Clayton, MO 63105
Phone: (314) 721-8427
Email: nicole@rafcoprop.com
ABC Condo Association c/o Rafco Properties
7700 Forsyth Blvd, Ste 100, Clayton, MO 63105
Phone: (314) 721-8427
Email: nicole@rafcoprop.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Octagon box located in the hoistway at the 1st & 2nd floor is missing a cover. | 11/5/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 4 Inch box located behind the counterweight guard in the pit has a missing cover plate. | 11/5/2018 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 11/5/2018 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/5/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 11/30/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | A permanent ladder shall be provided for access to the overhead machine room. | 9/13/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room in a noncombustible frame with a clear protective vision plate over it. | 11/30/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | Yes | The counterweight runby is insufficient to allow the car to reach the up final limit switch. Elevator is Red Tagged. | 9/7/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | A permanent ladder shall be provided for access to the overhead machine room. The space in the stairwell may be inadequate for the installation of a ladder, in that case an application for a variance should be submitted by the owner. | 11/30/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Feeder locations for the main branch circuit shall be marked on the disconnect. | 11/30/2023 |