Inspection
Inspection Details
Equipment ID
21452
21452
Inspection Date
12/19/2023
12/19/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
NA
NA
External ID
3ddec54a-fa2c-4101-96b5-7827420b3c0b
3ddec54a-fa2c-4101-96b5-7827420b3c0b
Location
Fairfield Inn and Suites
130 Crossroads South Dr, Wentzville, MO
Phone: (417) 883-1204
130 Crossroads South Dr, Wentzville, MO
Phone: (417) 883-1204
Owner
Attn: Fairfield Inn Wentzville
Midas Wentzville, LLC
1804 Borman Circle Dr, Ste 100, St. Louis, MO 63146
Phone: (314) 764-4262
Email: kprainito@midashospitality.com
Midas Wentzville, LLC
1804 Borman Circle Dr, Ste 100, St. Louis, MO 63146
Phone: (314) 764-4262
Email: kprainito@midashospitality.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.36 - Hydraulic Cylinders | 3.18.3 | Yes | No | Jack seal leaking needs to be replaced. | 12/9/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean pit of dirt and oil. | 3/19/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 Guards Between Adjacent Pits | No | No | Repair pit light | 1/8/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Empty jack drip pans in pit | 1/8/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Provide monthly fire service test & document on log posted in machine room | 1/8/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair phone in car | 1/1/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean drip pans in pit | 3/10/2022 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.11.3.1.5(a) | No | No | Remove oil from pit floor 2.2.2.3 | 12/21/2022 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.11.3.1.5(a) | No | No | Empty drip pan in the pit 2.2.2.3 | 12/21/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service test and document on log in machine room 1206.3 | 12/21/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove oil from pit floor written up last inspection still not completed 30 day maximum | 12/18/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Empty drip pans written up last inspection and still not completed 30 day maximum | 12/18/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Battery lowering unit not working 30 day maximum | 12/19/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication/phone not working in car 30 day maximum | 12/19/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Empty drip pans and remove oil from the pit floor | 1/20/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | Tag overspeed valve that was tested 11/15/23 | 1/20/2025 |