Inspection
Inspection Details
Equipment ID
7125
7125
Inspection Date
12/13/2023
12/13/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
19
19
External ID
2791ad1e-c438-4177-a60c-57f46e8976f8
2791ad1e-c438-4177-a60c-57f46e8976f8
Location
Gallery 515
515 Olive St, St. Louis, MO
Phone: (314) 241-5964
515 Olive St, St. Louis, MO
Phone: (314) 241-5964
Owner
Attn: Brandonview LLC
Brandonview LLC
515 Olive St, Ste 106, St. Louis, MO 63101
Phone: (314) 421-4500
Alt Phone: (314) 328-7900
Email: mgummels@stlluxury.com
Brandonview LLC
515 Olive St, Ste 106, St. Louis, MO 63101
Phone: (314) 421-4500
Alt Phone: (314) 328-7900
Email: mgummels@stlluxury.com
Billing
Attn: Brandonview LLC
Brandonview LLC
515 Olive St, Ste 106, St. Louis, MO 63101
Phone: (314) 421-4500
Alt Phone: (314) 328-7900
Email: gallery515@stlluxury.com
Brandonview LLC
515 Olive St, Ste 106, St. Louis, MO 63101
Phone: (314) 421-4500
Alt Phone: (314) 328-7900
Email: gallery515@stlluxury.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 3/15/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/15/2022 |
| A17.1-2016 : Elevators | 1.4 - Sills and car floor | 2.11.10.2 | No | No | Illumination at Landing Sills: The building corridors shall be so lighted that the illumination at the landing sills, when an elevator is in service, shall be not less than 10 fc. Note: Some lobbies are under construction, and not lighted. | 3/15/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The buffers, pit channels, and/or the compensating sheave assembly, which are visible from the pit access door, shall be marked with the car identification number with a minimum of 2 inches in height and of a contrasting color to its background. | 3/15/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 3/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 2.29.1 | No | No | The identification number for each elevator shall be painted on, engraved, or securely attached adjacent to or on every elevator entrance at the designated level, and shall be a minimum of 3 inches in height. | 7/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | No | No | Permanent electric lighting shall be provided in all machine rooms and machinery spaces. The illumination shall be not less than 19 foot-candles at the floor level. Note: The secondary space is not lighted. | 7/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Access doors to machine rooms and overhead machinery spaces shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. Note: The secondary access door doesn't meet these requirements. | 7/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Yes | No | Current State operating certificate shall be displayed in the equipment room in a non-combustible fram. (previously cited re-inspection to enforce) | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.4 - Sills and car floor | 2.11.11.1 | Yes | No | The building corridors shall be so lighted that the illumination at the landing sills, when an elevator is in service, shall be not less than 10fc. (previously cited re-inspection to enforce) | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.3.2 | Yes | No | The buffers, Governor tail sheave, and/or the compensating sheave assembly, which are visible from the pit access door, shall be marked with the car identification number with a minimum of 2 inches in height and of a contrasting color to its background. (cited previously re-inspection to enforce) | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | Yes | No | Permanent electric lighting shall be provided in all machine rooms and machinery spaces. The illumination shall be not less than 19 foot-candles at the floor level in the Primary Machine room (previously cited re-inspection to enforce) | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | Yes | No | Access doors to machine rooms and overhead machinery spaces shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. (previously cited re-inspection enforce) | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.28 - Counterweight and counterweight buffer | 2.21 | No | No | Bottom counterweight roller shall be replaced. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.8 - Top emergency exit | 8.11.2.1.3(l) | No | No | Top emergency exit shall be properly secured. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | : Pit shall be kept clean. Remove excess debris, Water noted in pit as well. |