Inspection
Inspection Details
Equipment ID
9357
9357
Inspection Date
10/30/2018
10/30/2018
Inspection Type
Reinspection
Reinspection
Inspector Name
Ronald Edwards
Ronald Edwards
Mechanic Name
Brent Bonham
Brent Bonham
Relief Valve Pressure
n/a
n/a
Slide
Governor Rope Pull
Door Closing Force
n/a
n/a
External ID
152b1148-b556-45b0-9169-4d51e31bbe08
152b1148-b556-45b0-9169-4d51e31bbe08
Location
The National Golf Club of KC
6700 N NATIONAL DR, PARKVILLE, MO
6700 N NATIONAL DR, PARKVILLE, MO
Owner
The National Golf Club of KC
PO BOX 14146, PARKVILLE, MO 64152-0646
PO BOX 14146, PARKVILLE, MO 64152-0646
Billing
Attn: The National Golf Club of KC
PO BOX 14146, PARKVILLE, MO 64152-0646
PO BOX 14146, PARKVILLE, MO 64152-0646
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarmbell not working | 10/30/2018 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Emg. Lt. not working | 9/14/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt. displayed | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | Yes | No | battery lowering not working | 8/5/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | oil an oily rags on pit floor | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | car lights not guarded or sleeved | |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.11.3.1.1(r) | Yes | No | car door locking device not working 8.6.4.13.1(L) | 8/5/2022 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | Yes | No | Repair the battery lowering. | 8/18/2023 |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.19.16 | Yes | No | Repair the door restrictor. | 8/18/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the pit | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Guard the cab lights. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | non elevator equipment in machine room | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | car lts. need to be guarded | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | pit needs to be cleaned | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | meterials not related to maint or operation of the elev. need to be removed from mach. room | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | battery lowering failed | 8/22/2025 |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | Yes | No | door restrictor not working | 8/22/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt displayed | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | materials unrelated to elev stored in mach. room | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | car lighting needs to have cover put over box an tubes guarded |