Inspection
Inspection Details
Equipment ID
2422
2422
Inspection Date
12/8/2023
12/8/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
22
22
External ID
d096ac4b-8314-4df7-99c2-897f5f0efdc6
d096ac4b-8314-4df7-99c2-897f5f0efdc6
Location
Midwest Regional Bank
135 N Meramec Ave, Ste 1, Clayton, MO
Phone: (314) 338-7912
135 N Meramec Ave, Ste 1, Clayton, MO
Phone: (314) 338-7912
Owner
Attn: Tamara Williamson
Midwest Regional Bank
1215 Fern Ridge Pkwy, Ste 214, St. Louis, MO 63141
Phone: (314) 853-3765
Email: balkebrown@avidbill.com
Midwest Regional Bank
1215 Fern Ridge Pkwy, Ste 214, St. Louis, MO 63141
Phone: (314) 853-3765
Email: balkebrown@avidbill.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | In cab emergency telephone shall work. | 2/11/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | A current tested fire extinguisher shall be provided in the elevator machine room. | 1/28/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | Yes | No | Replace the missing sight edge on hoistway door, B Floor, left side. | 1/28/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post the current state operating certificate. | 1/28/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The ETS system and NTS system shall be tested. | 12/21/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. The extinguisher is expired. | 3/8/2022 |
| A17.1-2016 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 2.10.2.3 Toe Board | No | No | Missing toe board on car top | 6/24/2024 |
| A17.1-2016 : Elevators | 3.2 - Car top light and outlet | 2.14.7.1.4 | No | No | Provide means to have 10fc of light anywhere on car top. | 6/24/2024 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | No | No | Beveling required on hoistway ledges exceeding 4”. | 6/24/2024 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | Missing braille/tactile plates on all entrances. | 6/24/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 12/16/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | The pit light shall be operational. | 12/16/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.1(h) Call Cancel Button (Re-Inspection) | Yes | No | When the car is on phase two fire service and the call cancel button is activated, all registered calls shall be canceled and a traveling car shall stop at or before the next available landing. The CCB cancels the car calls as required, but the car continues to run until reaching the terminal floor. This will happen in both the up and down directions when running on phase two. | 7/24/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.1(h) Call Cancel Button (Re-Inspection) | Yes | No | When the car is on phase two fire service and the call cancel button is activated, all registered calls shall be canceled and a traveling car shall stop at or before the next available landing. The CCB cancels the car calls as required, but the car continues to run until reaching the terminal floor. This will happen in both the up and down directions when running on phase two. Violation still not corrected as of 7/24/25. This violation must be corrected immediately or the unit may be red tagged out of service. | 9/4/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate is expired. | 4/1/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm bell not working. | 4/1/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lights not working. | 4/1/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certi?cate required in machine room. | 4/10/2026 |