Inspection
Inspection Details
Equipment ID
2423
2423
Inspection Date
12/8/2023
12/8/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
23
23
External ID
1da3598a-2b8d-450f-ab0f-7c78e224d4e4
1da3598a-2b8d-450f-ab0f-7c78e224d4e4
Location
Midwest Regional Bank
135 N Meramec Ave, Ste 1, Clayton, MO
Phone: (314) 338-7912
135 N Meramec Ave, Ste 1, Clayton, MO
Phone: (314) 338-7912
Owner
Attn: Tamara Williamson
Midwest Regional Bank
1215 Fern Ridge Pkwy, Ste 214, St. Louis, MO 63141
Phone: (314) 853-3765
Email: balkebrown@avidbill.com
Midwest Regional Bank
1215 Fern Ridge Pkwy, Ste 214, St. Louis, MO 63141
Phone: (314) 853-3765
Email: balkebrown@avidbill.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | In cab emergency telephone shall work. | 2/11/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post the current state operating certificate. | 1/28/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | x | Replace the missing/broken hoistway door beak tension spring, 2nd Floor. | 1/28/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.11.2.1.5(b) | x | Provide code required minimum counterweight runby clearance. | 1/28/2020 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | x | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 6/2/2021 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | The heat and shunt trip in the machine room shall be removed. | 6/2/2021 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. The extinguisher is expired. | 3/8/2022 | ||
| A17.1-2016 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 2.10.2.3 Toe Board | x | Missing toe board on car top. | 12/8/2023 | |
| A17.1-2016 : Elevators | 3.2 - Car top light and outlet | 2.14.7.1.4 | Provide means for 10fc of light anywhere on car top. | 6/24/2024 | ||
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Beveling required on hoistway ledge exceeding 4”. | 6/24/2024 | ||
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | Provide braille/tactile plates on all entrances. | 6/24/2024 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 12/16/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | x | The in car emergency lights shall be operational. Note: With the power to the car lighting branch circuit removed, the lights came on momentarily, then went out and did not come back on. | 7/24/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | The pit light shall be operational. | 12/16/2025 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | State operating certificate is expired. |