Inspection
Inspection Details
Equipment ID
24553
24553
Inspection Date
1/9/2024
1/9/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
John Palmer, Jr
John Palmer, Jr
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
9962ef67-9594-4ea1-b99d-21ff34d745dc
9962ef67-9594-4ea1-b99d-21ff34d745dc
Location
One Hundred Kingshighway
100 N Kingshighway, St. Louis, MO
Phone: (314) 991-1158
100 N Kingshighway, St. Louis, MO
Phone: (314) 991-1158
Owner
Attn: Kyle Bozoian
100 Kingshighway, LLC
32 N Dean Str, 2nd Fl, Englewood, NJ 07631
Phone: (314) 328-7770
Email: residentservices@liveat100.com
100 Kingshighway, LLC
32 N Dean Str, 2nd Fl, Englewood, NJ 07631
Phone: (314) 328-7770
Email: residentservices@liveat100.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | Fire service operation, smokes, heats, powered hoistway venting, and other associated items must be completed and tested. | 7/31/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 7/31/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.3 Provide Auxiliary Lighting | Yes | No | The emergency lighting shall be operational. | 7/31/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The alarm bell shall operate on auxiliary power. | 7/31/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.4 - Sills and car floor | 8.11.2.1.1(d) | Yes | No | The elevator floor and lobby floors must be finished and landings sills grouted. | 7/31/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | Yes | No | Permanent main line and lighting power shall be provided and shall have feeder locations marked. | 7/31/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | The penetrations in the hoistway shall be sealed with approved solid material. | 7/31/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Yes | No | A written maintenance control program (MCP) shall be in place to maintain the equipment in compliance with the requirements of Section 8.6. | 7/31/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | All electrical device and wireway covers shall be installed. | 7/31/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | A light switch, lighting, and GFCI receptacle must be installed in the overhead. | 7/31/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.8 | Yes | No | A light switch, light, and GFCI receptacle must be installed in the pit. | 7/31/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | A fire extinguisher must be provided and mounted convenient to the top landing hall door. | 7/31/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump pump shall be provided | Yes | No | Installation of the pit sump pump must be completed and the cover must be installed. | 7/31/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | The building fire control station must be installed and tested. | 7/31/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.42 Seismic (Earthquake protection) | 8.4.10 | Yes | No | The counterweight displacement system must be installed and tested. | 7/31/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | No | No | Hoistway door bottom retainers required | 7/19/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | No | No | Install wiring cover on hoist machine. Violation code 2.8.1 | 7/19/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete, need to test Emergency power. Re-inspection required | 1/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | Yes | No | EP/Lobby panel has key switches and jewels that indicate car #4 has EP. Per Kone, #4 is not on EP; remove switches and jewels for #4 that are not appropriate for the current configuration. | 7/23/2026 |