Inspection
Inspection Details
Equipment ID
1728
1728
Inspection Date
1/10/2024
1/10/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Bradley Rasnake
Bradley Rasnake
Mechanic Name
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
dcfbfeca-afc4-4de1-bd14-88bc228a1175
dcfbfeca-afc4-4de1-bd14-88bc228a1175
Location
Mercy Hospital Washington
901 E 5th St, Washington, MO
Phone: (636) 239-8088
Email: Ronald.jolly@mercy.net
901 E 5th St, Washington, MO
Phone: (636) 239-8088
Email: Ronald.jolly@mercy.net
Owner
Attn: Tara
Mercy Hospital East Communities
901 E 5th St, Washington, MO 63090
Phone: (636) 239-8086
Email: Tara.Carey@mercy.net
Mercy Hospital East Communities
901 E 5th St, Washington, MO 63090
Phone: (636) 239-8086
Email: Tara.Carey@mercy.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | The ventilation fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. | 7/10/2020 |
| conversion | conversion | n/a | No | No | The ?Elevator Inspection? operation does not work in the elevator controller. Repair operation to work as designed. | 7/10/2020 |
| conversion | conversion | conversion - reinspect | Yes | No | The fireman's emergency service phase I and II operations were tested and the following deficiencies were noted: In phase II operation, the elevator car will not override the security feature on the car operating panel on the rear door. Security shall be overridden in fireman?s service. | 2/8/2019 |
| conversion | conversion | n/a | No | No | The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it also is a safety/code concern. Without motion, the switch deactivates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch to a conventional on/off switch. | 7/10/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | No | No | The ventilation fan on top of the car has become loose and shall be re-secured to the car top. | 7/10/2020 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | Yes | No | Sprinkler heads have been added to the elevator machine room without the required heat detectors to activate the shunt trip disconnect before the application of water. Heat detectors shall be installed within 2’ of each sprinkler head to activate the shunt trip disconnect. | 11/1/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The ventilation fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. At this time controller doors have been removed from the controller allowing exposed wiring to be accessible to damage. | 7/10/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The “Elevator Inspection” operation does not work in the elevator controller. Repair operation to work as designed. | 7/10/2020 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)9 | No | No | Sprinkler heads have been added to the elevator machine room without the required heat detectors to activate the shunt trip disconnect before the application of water. Heat detectors shall be installed within 2’ of each sprinkler head to activate the shunt trip disconnect. | 7/10/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. | 7/6/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The ventilation fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. At this time controller doors have been removed from the controller allowing exposed wiring to be accessible to damage. | 12/9/2020 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Standby power needs to be tested. Re-inspection required | 11/15/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone line does not call out. Re-inspection required | 11/15/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone line does not call out. Re-inspection required | 1/10/2024 |