Inspection
Inspection Details
Equipment ID
3453
3453
Inspection Date
10/2/2017
10/2/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
27
27
External ID
Location
AT&T- St. Joseph
320 North 10th St, St. Joseph, MO
Phone: (816) 271-2582
320 North 10th St, St. Joseph, MO
Phone: (816) 271-2582
Owner
AT&T- Elevator Management c/o Lerch Bates
4201 Northview Drive Suite 314, Bowie, MO 20716
4201 Northview Drive Suite 314, Bowie, MO 20716
Billing
Attn: AT&T- Elevator Management c/o Lerch Bates
4201 Northview Drive Suite 314, , MD 20716
4201 Northview Drive Suite 314, , MD 20716
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Emergency phone does not operate | 10/23/2018 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Governor rope has excessive amount of wire breaks and needs to be replaced | 6/22/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Need to post fire service instructions inside and outside the elevator. | 6/22/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Visual and audible signals do not operate when elevator is on fire service. | 6/22/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Smoke senstive door reopening device is not disabled during fire service phase2 operation. | 6/22/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Test fire service operation monthly and provide documentation. | 3/2/2023 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Visual (light) and audible (buzzer) signal do not function during fire recall operation. Not red tagged | 4/28/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | Must make Visual and Audio Fire service signal operable | 6/1/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Must provide Fire service operational instructions both car and hall | 3/2/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Must provide monthly fire service test log | 3/2/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | 5.100(2) Must post Current state operating Cert. 5.100(2) | 8/1/2023 |