Inspection
Inspection Details
Equipment ID
6462
6462
Inspection Date
10/30/2018
10/30/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gerald Glynn
Gerald Glynn
Mechanic Name
Timothy Driver
Timothy Driver
Relief Valve Pressure
360
360
Slide
Governor Rope Pull
Door Closing Force
13
13
External ID
0f381934-6d5d-4e6b-b688-31342ec75156
0f381934-6d5d-4e6b-b688-31342ec75156
Location
CFI-XPO
4701 E 32ND ST, JOPLIN, MO
4701 E 32ND ST, JOPLIN, MO
Owner
CFI (XPO)
4701 E 32ND ST, JOPLIN, MO 64804-3482
4701 E 32ND ST, JOPLIN, MO 64804-3482
Billing
Attn: CFI (XPO)
4701 E 32ND ST, JOPLIN, MO 64804-3482
4701 E 32ND ST, JOPLIN, MO 64804-3482
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | 12/22/20: Emergency/auxiliary lighting shall work with power loss. | 3/10/2022 | |
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | 12/22/20: 2-way communication device shall work and give proper location | 3/10/2022 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | G(1). Battery Lowering shall work. Repair or replace. | 5/23/2022 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | G(1)/8.6.1.4 : MCP shall be kept in equipment room, and Fire service testing log, recorded monthly. | 5/23/2022 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | G(1) Repair damaged car riding lanterns (direction arrows) | 5/23/2022 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | 12/22/20: Emergency/auxiliary lighting shall work with power loss. | 3/10/2022 | |
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | 12/22/20: 2-way communication device shall work and give proper location | 3/10/2022 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | A17.1-2016:8.6.1.4 :Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil loss log and Fire service testing log, recorded monthly. | 5/23/2022 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Replace missing fishplate bolt. | 5/23/2022 | ||
MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | x | Replace damaged limit switch rollers. | 5/20/2022 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.3.2.2 Cylinders Test shall be performed | x | x | REDTAG. PISTON PACKING BLOWOUT DURING TEST. REPAIR AS NEEDED. REINSPECT TO RETURN TO SERVICE (“Stop ring test”) | 5/20/2022 |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.3.2.2 Cylinders Test shall be performed | x | REDTAG. PISTON PACKING BLOWOUT DURING TEST. REPAIR AS NEEDED. REINSPECT TO RETURN TO SERVICE (“Stop ring test”) | 5/20/2022 | |
MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | x | Replace damaged limit switch rollers. | 5/20/2022 |