MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
In car emergency telephone shall work.
|
1/13/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
In car emergency phone shall be operational.
|
1/21/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.11.2.1.2(k)
|
|
|
The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.14 - Code data plate
|
8.9
|
|
|
Install a code data plate. It shall read: A17.1-2004.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Rooms and Machinery Spaces
|
|
|
Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2 (Re-Inspection)
|
x
|
|
Pipes that convey liquid, vapors, or gas and cross overhead or come in close proximity to elevator equipment shall be guttered or guarded
|
1/10/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Up to date operating certificate required in the machine room.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
3.26.10 (Auxiliary Power)(Re-Inspection)
|
x
|
|
Auxiliary power lowering does not work. Take corrective action and re-test.
|
1/14/2025
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.12 - Car enclosure
|
2.14
|
|
|
2.14.7.4 - Missing ceiling tiles inside car.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
3.26.10 (Auxiliary Power)(Re-Inspection)
|
x
|
|
Auxiliary power lowering does not work. Take corrective action and re-test. (2nd Notice)
|
3/13/2025
|