Inspection
Inspection Details
Equipment ID
15933
15933
Inspection Date
1/11/2024
1/11/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Douglas Miller
Douglas Miller
Relief Valve Pressure
470
470
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
17
17
External ID
2c6164d6-2d76-4e76-a583-243bd50f6f15
2c6164d6-2d76-4e76-a583-243bd50f6f15
Location
Rauch Hall
209 S Kingshighway St, St. Charles, MO
Phone: (000) 000-0000
209 S Kingshighway St, St. Charles, MO
Phone: (000) 000-0000
Owner
Attn: Joyce Norman
Lindenwood University
209 S Kingshighway St, St. Charles, MO 63301
Phone: (636) 949-4922
Alt Phone: (636) 579-1235
Email: JNorman@lindenwood.edu
Lindenwood University
209 S Kingshighway St, St. Charles, MO 63301
Phone: (636) 949-4922
Alt Phone: (636) 579-1235
Email: JNorman@lindenwood.edu
Billing
Attn: Accounts Payable
Lindenwood University
209 S Kingshighway St, St. Charles, MO 63301
Phone: (636) 949-4922
Alt Phone: (636) 579-1235
Email: AccountsPayable@lindenwood.edu
Lindenwood University
209 S Kingshighway St, St. Charles, MO 63301
Phone: (636) 949-4922
Alt Phone: (636) 579-1235
Email: AccountsPayable@lindenwood.edu
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | An MCP shall be in place as specified in A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 | 8/31/2022 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | 8.6.1.7.5 - The emergency lowering device shall be operational. | 12/18/2020 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 8/31/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The alarm bell shall operate on auxiliary power. | 12/18/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall work on auxiliary power. | 12/18/2020 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | 8.6.1.7.5 - The emergency lowering device shall be operational. | 12/8/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency telephone shall be answered. Phone is now operational on auxiliary power, but the phone is not being answered. | 12/8/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 1/31/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 1/31/2022 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | The auxiliary power lowering operation shall be functional. | 8/18/2025 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | Yes | No | Where an additional power source is connected to the load side of the disconnecting means, the disconnecting means required in Section 620-51 shall be provided with an auxiliary contact that is positively opened mechanically and the opening shall not be solely dependent on springs. This contact shall cause the additional power source to be disconnected from its load when the disconnecting means is in the open position. Note: The auxiliary contact required for the auxiliary power lowering is not present. | 8/18/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.8 Switch Keys | No | No | The fire service phase one key-switch bezel shall be legible. | 1/21/2026 |