Inspection
Inspection Details
Equipment ID
12185
12185
Inspection Date
9/25/2018
9/25/2018
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
John Ryan
John Ryan
Mechanic Name
Dustin Arnett
Dustin Arnett
Relief Valve Pressure
Slide
4"
4"
Governor Rope Pull
80/380
80/380
Door Closing Force
23
23
External ID
5712172e-7725-44e1-8702-687b7fb54bcf
5712172e-7725-44e1-8702-687b7fb54bcf
Location
Hillside Manor
1265 MCLARAN AVE, SAINT LOUIS, MO
1265 MCLARAN AVE, SAINT LOUIS, MO
Owner
SW Management
7434 SKOKIE BLVD, SKOKIE, IL 60077-3341
7434 SKOKIE BLVD, SKOKIE, IL 60077-3341
Billing
Attn: SW Management
7434 SKOKIE BLVD, SKOKIE, IL 60077-3341
7434 SKOKIE BLVD, SKOKIE, IL 60077-3341
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Replace the hoist ropes. | 10/8/2019 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | x | The car door restrictor shall work. | 10/8/2019 | |
MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | Phase 2 fire service shall work. Phase 2 fire service shall be tested. | 10/8/2019 |
MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)7 | x | x | Full load test tags where not on equipment. Attach tags or Cat 5 test shall be performed. | 5/28/2021 |
MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | When key is engaged for Phase I fire service, elevator does not return to the designated floor. Red tagged. | 5/28/2021 |
MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | Phase II fire service does not operate. Red tagged. | 5/28/2021 |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Jumpers in fire service panel must be removed. | 4/27/2022 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Electrical wiring for the machine room light must be ran in an enclosed circuit, raceway and comply with NFPA 70. | 4/27/2022 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Electrical prints shall be provided in the machine room. | 4/27/2022 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Non-elevator related material needs to be removed from machine room. | 8/22/2024 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Traveling cable is not in protective raceway in machine room. | 8/22/2024 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Covers are missing in machine room raceway. | 8/22/2024 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | The top of the car is dirty. Clean the car top. | 8/22/2024 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | The hoistway is dirty. Clean the hoistway. | 8/22/2024 |