Inspection
Inspection Details
Equipment ID
23591
23591
Inspection Date
1/19/2024
1/19/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Thomas Suedkamp
Thomas Suedkamp
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25
25
External ID
c80439b1-7832-4b74-8241-de698af27166
c80439b1-7832-4b74-8241-de698af27166
Location
Two Twelve Clayton Apartments
212 S Meramec Ave, Clayton, MO
Phone: (314) 721-1212
212 S Meramec Ave, Clayton, MO
Phone: (314) 721-1212
Owner
Attn: 2B Residential
c/o Two Twelve Clayton
212 S Meramec Ave, Clayton, MO 63105
Phone: (314) 721-1212
Email: 212claytoninvoices@2bresidential.com
c/o Two Twelve Clayton
212 S Meramec Ave, Clayton, MO 63105
Phone: (314) 721-1212
Email: 212claytoninvoices@2bresidential.com
Billing
Attn: Amy Beckmann
Two Twelve Clayton
212 S Meramec Ave, Clayton, MO 63105
Phone: (314) 721-1212
Email: 212claytoninvoices@2bresidential.com
Two Twelve Clayton
212 S Meramec Ave, Clayton, MO 63105
Phone: (314) 721-1212
Email: 212claytoninvoices@2bresidential.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.11.2.1.5(b) | Yes | No | Provide code compliant minimum counterweight runby. | 10/29/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Provide pit ladder rungs to be non-slip type. | 2/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Provide code compliant pit lighting. | 2/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 2/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide a code compliant MCP including onsite documents. | 2/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Standby power operation of the elevator shall be tested. | 8/10/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 8.11.2.1.4(h) | No | No | Hoistway walls shall have smooth surfaces. Drywall screws shall not protrude into the hoistway. | 2/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | The top of the car and the hoistway shall be cleaned. | 2/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean. Clean the pit. | 2/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 11/2/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | Yes | Yes | The suspension cables shall be replaced and tagged. The ropes are undersized, bottoming out in the gauge in various spots, have crown breaks, and are in the presence of considerable rouge. This meets the replacement criteria outlined in A17.6 - 1.10. Additionally, the rouge shall be removed from the hoistway, machine, and brakes. - Elevator Red Tagged. | 1/27/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | The category 5 test/annual inspection was halted after the condition of the ropes was discovered. After the ropes are replaced, any remaining testing items, as well as, the complete category 5 test shall be completed. | 1/27/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | The hoist ropes have been replaced. The annual inspection and category 5 test shall be completed. | 3/29/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.3 | Yes | Yes | This unit has been RED TAGGED. The brakes are not holding 125% or 100% load. | 4/4/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | While trying to complete the annual and category 5 test, the unit had to be red tagged. The following items are the only items that were completed. Anything not listed here still needs to be tested: Items completed - The hoistway was run including the pit and passed. The governor was tested as required and passed. The emergency lights, alarm bell and phone were tested and passed. The rest of the tests have yet to be performed. | 4/4/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | The red tag has been removed and the brake is now holding 125%. The following items are the only items that were completed. Anything not listed here still needs to be tested: Items completed - The hoistway was run including the pit and passed. The governor was tested as required and passed. The emergency lights, alarm bell and phone were tested and passed. The rest of the tests have yet to be performed. | 6/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.16.8 | Yes | Yes | This unit has been red tagged. The brakes aren't holding 125% load. | 6/23/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | The hoistway was run including the pit and passed. The governor was tested as required and passed. The emergency lights, alarm, and phone were tested and passed. All other remaining testing items need to be completed. | 6/23/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.5 - Traveling cables | 2.8.1 | No | No | Properly repair or replace travel cable. Previously repaired with "duct tape". | 4/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | Emergency power operating and fire service shall be tested to complete inspection. | 1/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device is not functioning and needs repaired. | 12/31/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current state operating certificate shall be displayed in the machine room in a non-combustible frame. | 12/31/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.1.3.3 | No | No | Wiring for the cellular gateway is draped across the control space and needs to be re-routed around the perimeter of space and properly supported. | 12/31/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.7 - Car door or gate | 2.14.4 | No | No | Door open button on rear car station is missin label identifying operation of button. Replace missing label. | 12/31/2025 |