Inspection
Inspection Details
Equipment ID
10867
10867
Inspection Date
1/20/2024
1/20/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
19
19
External ID
2bc28ded-ed29-4316-a88c-df425cfbfa26
2bc28ded-ed29-4316-a88c-df425cfbfa26
Location
St. Louis Place
200 N Broadway, St. Louis, MO
Phone: (314) 241-0082
200 N Broadway, St. Louis, MO
Phone: (314) 241-0082
Owner
Attn: Cushman & Wakefield
BPRE St. Louis Holdings, LLP
200 N Broadway, Ste 820, St. Louis, MO 63102
Phone: (314) 241-0082
Email: tiara.nash@cushwake.com
BPRE St. Louis Holdings, LLP
200 N Broadway, Ste 820, St. Louis, MO 63102
Phone: (314) 241-0082
Email: tiara.nash@cushwake.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | REpair phone in car | 1/9/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 3/22/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service test & document on log | 3/22/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replacehoist ropes--red rouge & reduced diameter within 30 days | 1/26/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Replace missing duct cover on top of the car | 3/22/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing section of the duct cover on the top of the car | 3/22/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Repair/replace greenfield to fan top of the car | 3/22/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace hoist ropes red rouge reduced diameter within 30 days | 2/8/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Repair emergency light in the car | 2/8/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the phone in the car | 2/8/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 2/5/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 1/20/2024 |
| A17.1-2016 : Elevators | 3.20 - Governor rope | 8.6.3.4 | Yes | No | Governor ropes has multiple strands broken needs replacement 30 maximum on respection | 2/14/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Phase II fire service operation not working 14 day maximum on reinspection | 2/14/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2 Replacement of Suspension Means (Re-Inspection) | Yes | No | Inspection for replacement of governor rope has not been completed yet. State has granted an extension | 6/3/2024 |
| MO Minimum : Elevators | (J) - Counterweights | (J)3 | No | No | Bottom runby for counterweight is 0". Counterweight just touches buffer at top landing. Shorten Ropes for proper clearance. | 4/6/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | PM/Repair/callback logs not being consistently documented. | 4/6/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)6 | No | No | Hoistway doors have missing or loose guides on 8, 10, 12th floors. Repair/replace as needed. | 4/6/2026 |