Inspection
Inspection Details
Equipment ID
14383
14383
Inspection Date
10/18/2017
10/18/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
Location
Congress Apartments
275 Union Blvd, St Louis, MO
Phone: (314) 367-7900
275 Union Blvd, St Louis, MO
Phone: (314) 367-7900
Owner
City Club Apts
31700 Middlebelt Rd Ste 140, Farmington Hills, MI 48334
31700 Middlebelt Rd Ste 140, Farmington Hills, MI 48334
Billing
Attn: City Club Apts
275 Union Blvd, , MO 63108
275 Union Blvd, , MO 63108
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | In cab emergency telephone shall work. | 10/18/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Provide a code compliant pit ladder. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 8.11.2.1.3(r) | No | No | Pipes carrying liquids are not permitted in the hoistway. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display the current state operating certificate. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | An ABC type for extinguisher shall be kept in the machine room. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Provide a code compliant pit ladder. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean and dry. Clean the pit. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide a code compliant MCP including onsite documents. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | Clean the car top. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.4 - Sills and car floor | 8.11.2.1.1(d) | No | No | The elevator floor shall be repaired. Currently a tripping hazard. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | All phases of fire service and the buffer test shall be completed to finish the annual inspection. | 4/13/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.6 Stop Switches in Pit (Re-Inspection) | Yes | No | An additional pit stop switch shall be installed adjacent to the pit ladder and approximately 47 inches above the pit floor. | 4/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The following tests have yet to be performed and witnessed: rated speed buffer tests, unintended movement tests, 125% load tests, and rated speed full load safety test. | 4/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.6 Stop Switches in Pit (Re-Inspection) | Yes | No | An additional pit stop switch shall be installed adjacent to the pit ladder and approximately 47 inches above the pit floor. | 6/7/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The following tests have yet to be performed and witnessed: rated speed buffer tests, unintended movement in the down direction with 125%, 125% load tests, and rated speed full load safety test. | 6/7/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.6 Stop Switches in Pit (Re-Inspection) | Yes | No | An additional pit stop switch shall be installed adjacent to the pit ladder and approximately 47 inches above the pit floor. | 3/6/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.7 Firefighters' Emergency Operation: Operating Procedures | No | No | Phase 1 fire service instructions shall be provided in the elevator lobby. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | No | No | "In case of fire" signage is required at all landings. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | No | No | Pipe runs entire hoistway is not allowed. Remove, enclose, or apply for a variance. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Elevator shall be marked inside of the car as Elevator #1. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.4 Means for Manual Release | Yes | No | Emergency brake release module shall be tested. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Controller UIT/interface display input buttons not working. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire service test log is not being properly documented. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Machine room shall be kept free of excess debris (boxes, used parts, etc). | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | Provide machine room ventilation to meet OEM temperature/humidity requirements. Mini-split AC is not working, temp unit in place is not sufficient for room requirements. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean and dry. Remove excess debris. |