Inspection
Inspection Details
Equipment ID
12824
12824
Inspection Date
10/22/2018
10/22/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
David Tiemann
David Tiemann
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
16
16
External ID
fdc8d82d-375a-40d4-99c5-9f0a43351523
fdc8d82d-375a-40d4-99c5-9f0a43351523
Location
Drummond Hall
3691 RUTGER ST, SAINT LOUIS, MO
3691 RUTGER ST, SAINT LOUIS, MO
Owner
St. Louis University
3500 LINDELL BLVD, SAINT LOUIS, MO 63103-1021
3500 LINDELL BLVD, SAINT LOUIS, MO 63103-1021
Billing
Attn: St. Louis University
3500 LINDELL BLVD, SAINT LOUIS, MO 63103-1021
3500 LINDELL BLVD, SAINT LOUIS, MO 63103-1021
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light does not work. | 2/26/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in cab does not work. Re-inspection required | 10/26/2023 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | Yes | No | In car stop switch will not turn, needs to be replaced. Re-inspection required | 10/26/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire service Phase II key switch will not turn, needs to be replaced. Re-inspection required | 10/26/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Repair large hole in machine room wall | 11/25/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Install fire extinguisher in machine room | 11/25/2025 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | Yes | No | In car stop switch will not turn, needs to be replaced. Noted on a previous report. Re-inspection required. If not repaired in 14 days the elevator shall be removed from service. | 12/27/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | 8.6.4.19.6 Fire service Phase II key switch will not turn, needs to be replaced. Noted on a previous report. Re-inspection required. If not repaired in 14 days the elevator shall be removed from service. | 12/27/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Repair large hole in machine room wall. Noted on a previous report. | 11/25/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit floor is covered in dust and debris. The pit shall be cleaned. | 11/25/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Yes | No | The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed. | 12/27/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | A machine room lighting fixture was not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. | 11/25/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The Fire Service shall be tested before the inspection is completed. | 12/27/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Repair large hole in machine room wall. Noted on a previous reports. | 11/25/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | A machine room lighting fixture was not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. | 11/25/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Repair inoperative standby battery lowering |