Inspection
Inspection Details
Equipment ID
6785
6785
Inspection Date
2/2/2024
2/2/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
c6d1beaa-5d92-4e9c-a13e-2d5349173ef0
c6d1beaa-5d92-4e9c-a13e-2d5349173ef0
Location
Hilton Home 2 Suites
1221 Locust St, St. Louis, MO
Phone: (636) 579-3555
Email: dmgand64@gmail.com
1221 Locust St, St. Louis, MO
Phone: (636) 579-3555
Email: dmgand64@gmail.com
Owner
Attn: Brandi Jawher
Hilton Home 2 Suites
1221 Locust St, St. Louis, MO 63103
Phone: (636) 579-3555
Email: brandi.jawher@hilton.com
Hilton Home 2 Suites
1221 Locust St, St. Louis, MO 63103
Phone: (636) 579-3555
Email: brandi.jawher@hilton.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Existing cab emergency telephone does not work and shall be repaired and tested. | 5/30/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency telephone shall work. | 5/8/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | There is a hoistway door closing issue on the 1st floor. | 12/15/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a current state operating certificate in the elevator machine room. | 11/17/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | The pit lighting shall be operational. | 11/17/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | The machine room door shall be self-locking. | 11/17/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | The machine room lighting shall not be less than 10 ftc at the machine room floor. | 11/17/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | The car door restrictor shall be operational. | 10/21/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The emergency lighting shall be operational. | 10/21/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone shall be operational. | 10/21/2021 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide annual testing of elevators on emergency power. | 2/23/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Provide MCP. | 8/14/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Existing phone in car not working, no voltage. Repair as needed. | 2/23/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Lobby indicator for phone line loss not working, repair as needed. | 2/23/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevator appears to have emergency generator power, which needs to be scheduled and tested. Re-inspection required | 2/2/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car did not answer, needs repaired. Re-inspection required | 2/2/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to perform the following tests to complete inspection: unintended movement, fire service, emergency light & alarm, set safeties (no load). Re-inspection required | 2/2/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | Install cable data tag on car cable shackles | 7/28/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to install warning sign on pit door stating "Caution Elevator Pit" | 7/28/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator phone in car is not working. Re-inspection required | 2/20/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevator appears to have emergency generator backup power, which needs to be scheduled and tested to complete inspection. Re-inspection required | 2/20/2025 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 2.19.2 | Yes | Yes | Unintended Motion failed to limit the car travel to a maximum of 48" (Actual=67")in the down direction. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing Incomplete. Need to test: EP, F.S., Door#, CommLoss, 100%set, slide, UMup & UMdn, check MCP | |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.10.2.2.3(cc) | No | No | Hoist and Comp Ropes appear dry and showing beginning stages of “rouge”. Ropes shall be cleaned and lubricated per OEM recommendations. | |
| A17.1-2016 : Elevators | 3.17 - Door and gate equipment | 2.12 | No | No | Interlock at 11th floor shall have a proper cover(missing). | |
| A17.1-2016 : Elevators | 3.27 - Crosshead data plate | 8.7.2.17.3 Decrease in Rated Speed | No | No | Hoist and Governor Ropes shall have appropriate data tags |