Inspection
Inspection Details
Equipment ID
10641
10641
Inspection Date
2/1/2024
2/1/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
819f0a2e-4eb7-4b18-bd18-6ab845d89e92
819f0a2e-4eb7-4b18-bd18-6ab845d89e92
Location
Woodlands Plaza IV
11775 Borman Dr, Ste 110, St. Louis, MO
Phone: (314) 821-8440
Email: AAltman@stlcre.com
11775 Borman Dr, Ste 110, St. Louis, MO
Phone: (314) 821-8440
Email: AAltman@stlcre.com
Owner
Attn: Corbin Holtzman
Westport 215, LLC
1034 S Brentwood, Ste 300, St. Louis, MO 63117
Phone: (314) 409-3292
Email: choltzman@stlcre.com
Westport 215, LLC
1034 S Brentwood, Ste 300, St. Louis, MO 63117
Phone: (314) 409-3292
Email: choltzman@stlcre.com
Billing
Attn: Tracy Lewis
Westport 215, LLC
1034 S Brentwood Blvd, Ste 300, St. Louis, MO 63117
Phone: (314) 863-3700
Email: ap@stlcre.com
Westport 215, LLC
1034 S Brentwood Blvd, Ste 300, St. Louis, MO 63117
Phone: (314) 863-3700
Email: ap@stlcre.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | Securely mount variable resistor that is currently hanging with jumpers. | 3/1/2019 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | x | x | Fire service phase 2 call cancel shall work. | 12/11/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Fire extinguisher in the machine room is expired and shall be serviced or replaced. | 11/12/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | A code data plate is required. | 11/12/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display a copy of the current state operating certificate. | 11/12/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | An elevator maintenance log shall be kept on-site. | 11/12/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | A monthly fire service testing log shall be kept on-site. | 11/12/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 1/8/2021 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 11/21/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | x | The restrictor is not functioning properly. Corrective action is needed. The restrictor shall be operational in the absence of main power. | 12/19/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | A two-way communication device shall give proper location message. No location is being given. Also, agent said I was clear but the speaker is very choppy. | 2/1/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/21/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag. | 11/21/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. | 11/21/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | x | Overspeed valve in pit shall be tested. Some piping and possibly jack were replaced and an overspeed valve was insalled, sealed, and tagged in 2010. Category 5 full load testing shall be completed in 2025. |