Inspection
Inspection Details
Equipment ID
1339
1339
Inspection Date
2/7/2024
2/7/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Timothy Trout
Timothy Trout
Mechanic Name
Michael Loftin
Michael Loftin
Relief Valve Pressure
520
520
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
24
24
External ID
8101068d-2b15-4e52-91d6-0256e27dcae7
8101068d-2b15-4e52-91d6-0256e27dcae7
Location
Penleigh Branson Row
3029A W 76 Country Blvd, Branson, MO
Phone: (417) 559-2348
Email: shannon@atlasmanagementcorp.com
3029A W 76 Country Blvd, Branson, MO
Phone: (417) 559-2348
Email: shannon@atlasmanagementcorp.com
Owner
Attn: Galen Drever
Drever Atelier Angel LLC
3029 W Hwy 76, Branson, MO 65616
Phone: (646) 717-4245
Email: galen@dreverpartners.com
Drever Atelier Angel LLC
3029 W Hwy 76, Branson, MO 65616
Phone: (646) 717-4245
Email: galen@dreverpartners.com
Billing
Attn: Manuel Rivers and Jessica Koonz
Property Managers: Atlas Asset Management S Corp
641 Lexington Ave, Fl 20, New York, NY 10022
Phone: (845) 532-6934
Email: payables@atlasmanagementcorp.com
Property Managers: Atlas Asset Management S Corp
641 Lexington Ave, Fl 20, New York, NY 10022
Phone: (845) 532-6934
Email: payables@atlasmanagementcorp.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Replace the car light as the tubes are burnt out. | 9/25/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Replace the faulty fire service key switch, as it is hard to get contact with the tumblers, otherwise the fire service works fine. | 9/4/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Replace the burnt out pit light | 9/25/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | 9/25/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.2 Minimum Illumination | No | No | Replace the burnt out light sin the car. | 10/27/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean up the pit | 10/27/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | 10/27/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Have the fire extinguisher re-certified | 10/27/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair or replace the emergency phone as it will not dial out | 10/27/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | REplace the burnt out light tubes in the car ceiling as 2 two are required to be working. | 10/27/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | remove dirt and rubbish from pit floor | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | provide car lighting | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | clean car top | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | provide current state certificate |