Inspection
Inspection Details
Equipment ID
12114
12114
Inspection Date
1/30/2024
1/30/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Benjamin Williams
Benjamin Williams
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
306ad05d-2493-4b37-a1ad-ae439a51d3a6
306ad05d-2493-4b37-a1ad-ae439a51d3a6
Location
MODOT- District Office
1590 Woodlake Dr, Chesterfield, MO
Phone: (314) 275-1509
Email: lawrence.joedicke@modot.mo.gov
1590 Woodlake Dr, Chesterfield, MO
Phone: (314) 275-1509
Email: lawrence.joedicke@modot.mo.gov
Owner
Attn: INTERAGENCY
MODOT-DISTRICT OFFICE/INTERAGENCY
1590 Woodlake Dr, Chesterfield, MO 63017
Phone: (314) 453-1709
MODOT-DISTRICT OFFICE/INTERAGENCY
1590 Woodlake Dr, Chesterfield, MO 63017
Phone: (314) 453-1709
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 12/6/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | The in car stop switch shall be inoperable while in flight, while on Phase 1 return. | 1/30/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | NFPA70 620.91 - Machine room disconnecting means shall be provided with a compliant mechanical auxiliary contact to disconnect the load from the auxiliary power supply operation. | 1/30/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | No | No | Machinery, controllers, tanks, disconnects shall be properly numbered conspicuously. | 3/4/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | MCP fire service testing must be properly documented monthly on log sheet. | 3/4/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Permanently mounted pressure gauge shall be replaced with a calibrated gauge, having a calibration sticker that shows that it has been calibrated within the last year or install fitting for use of a detachable & calibrated portable gauge. | 3/4/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher is expired. | 3/4/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Adjust up-thrust roller bearings for proper clearance to door hanger track. (Multiple floors) | 3/4/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher is expired. | 2/29/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | MCP fire service testing must be properly documented monthly on log sheet. | 2/29/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | The overspeed valve shall be tested with the rated load on or before the next annual test. | 10/30/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The auxiliary power lowering shall be tested and function properly. | 10/16/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | The OSV test on this unit was not performed and is due. This was not completed due to failure of the other unit at the facility. All other tests required for the inspection have been completed. The OSV shall be tested with a full load. | 10/16/2025 |